Measurements of Voltage Harmonics in 400 kv Transmission Network

Wielkość: px
Rozpocząć pokaz od strony:

Download "Measurements of Voltage Harmonics in 400 kv Transmission Network"

Transkrypt

1 R. Pawełek et al. Acta Energetca /9 (04) 7 34 Measurements of Voltage Harmoncs n 400 kv Transmsson etwork Authors Ryszard Pawełek Irena Wasak Maran Jurek Keywords voltage harmoncs, power qualty, power qualty measurements Abstract The paper deals wth the analyss of voltage harmoncs measurements performed n the 400 kv transmsson network. The voltage was measured by means of three transducers: resstve voltage dvder, nductve measurng transformer and capactve voltage measurng transformer. Instrument errors were estmated for measurng transformers wth reference to the harmonc values obtaned from the voltage dvder. DOI: 0.736/ssn Introducton Voltage harmoncs n hgh voltage networks are usually measured wth voltage measurng transformers. Varous types of voltage measurng transformers used n the power sector are desgned to work at the frequency of 50 Hz, and ther transfer characterstcs for hgher frequences are unknown. When analysng the equvalent crcut dagrams t should be noted how the nductance, capacty and numerous non-lneartes affect ther transfer characterstcs n respect of frequency. The need to montor the power qualty parameters n power networks has been ndcated for a long tme []. In order to perform an accurate measurement of voltage harmoncs (wh), frequency and ndvdual dsturbances (e.g. levels of overvoltages or dps), the transmsson network operator, PSE Operator SA, has nstalled a measurng resstve dvder n one of 400 kv statons n cooperaton wth Transformex sp. z o.o. A detaled techncal descrpton of the dvder s ncluded n [, 3]. Generally, a resstve dvder should be a lnear element n respect of frequency, and therefore should transfer voltage waveforms n transent and steady states of network operaton wthout any dstortons. Thus, t should be free from most defects that can be found n voltage measurng transformers. The dvder measurng propertes n ths respect have been confrmed by laboratory tests carred out by the Insttute of Electrcal Engneerng (Warszawa-Mędzylese) []. A resstve dvder was used to compare and evaluate the results of voltage harmonc measurements carred out wth the selected types of hgh voltage measurng transformers. On the bass of comparatve measurements t wll be possble to determne the usefulness of voltage measurng transformers n measurements of voltage harmoncs, and n some cases to specfy the correcton factors.. Measurements Measurements of voltage harmoncs n the transmsson network of 400 kv were performed usng the UP-0 analyser produced by the Swedsh company Unpower. Measurement sgnals of the same phase voltage were smultaneously entered to three ndependent voltage nputs n the analyser; the sgnals came from: resstve voltage dvder, nductve measurng voltage transformer and capactve voltage measurng transformer. The measurements were carred out for 7 days ( December 0, 9, December 0, ). Respectve values were measured contnuously (every half perod of voltage curve) and averaged n 0-mnute ntervals. The followng were measured: phase voltage ampltude, voltage dstorton factors, relatve (percentage) values of ndvdual harmoncs and ther phase angles. The results of measurements obtaned usng the resstve dvder, the transfer functon of whch s ndependent of frequency, were adopted as reference values and compared wth the results obtaned from the measurng transformers. Phase angles of respectve voltage harmoncs were determned n relaton to the phase angle of the fundamental harmonc measured usng the resstve dvder (φu(d) = 0 ). The 400 kv feld n whch the resstve dvder s nstalled s swtched perodcally; therefore the number of samples for each measured quantty s 494 n a perod of one week (rather than 008). Fg. shows changes n the rms value of phase voltage measured n dvder swtchng perods. Fg. shows changes n the rms value of voltage measured usng all three measurng transducers. 7

2 R. Pawełek et al. Acta Energetca /9 (04) 7 34 U [kv] tme [dd-mm-yy/hh:mm] Fg.. Changes n the dvder rms voltage n the measurement perod 3. Evaluaton of measurement results The accuracy of measurements of voltage harmoncs and ther phase angles by voltage measurng transformers were carred out accordng to the followng procedure: ( U U ) h%, h% σ Uh% = (). By analogy, the average values were determned based on the sets of harmonc phase angles measured usng respectve transducers: ϕh, ϕ h = (3) where: φ h, the value of h-th harmoncs n -th 0-mnute nterval and the standard devaton was specfed: = ( ϕh, ϕh) σ ϕ h (4) Resstve voltage dvder Relatve error was establshed for each ndvdual voltage harmonc obtaned usng (nductve or capactve) voltage measurng transformers wth the result from the resstve dvder used as a reference value: U [kv] 40 U h%, ( p) U h%, ( d ) δ Uh%, = 00% U (5) h%, ( d ) 0 00 tme [dd-mm-yy/hh:mm] where: U h%,(p) the relatve value of h-th harmonc n -th 0-mnute nterval measured usng the voltage measurng transformer, U h%,(d) the relatve value of h-th harmonc n -th 0-mnute nterval measured usng the resstve dvder, Fg.. Changes n voltage n the measurement perod then the average value and standard devaton for that error were establshed n accordance wth [6] and [7]:. The followng average values were determned based on the sets of relatve values of hgher harmoncs measured usng ndvdual transducers (resstve voltage dvder, nductve voltage measurng transformer and capactve voltage measurng transformer): U U h%, h% = 8 where: U h%, the average value of h-th harmonc n -th 0-mnute nterval, = 494 number of measurements and the standard devaton was specfed: () δuh%, δ Uh% = (6) ( δ δ ) Uh%, Uh% σ Uh% = (7) δ The angle error for measurements of respectve voltage harmoncs obtaned usng measurng transformers was determned n the same way: δ ϕ h, = ϕh, ( p) ϕh, ( d ) (8) where: φ h,(p) the phase angle value of h-th harmonc n -th 0-mnute nterval measured usng the voltage measurng transformer, φ h,(d) the phase angle value of h-th harmonc n -th 0-mnute nterval measured usng the resstve dvder, then the

3 THD [%] R. Pawełek et al. Acta Energetca /9 (04) 7 34 average value and standard devaton for that error were establshed n accordance wth [9] and [0]: δϕh, δ ϕh = (9) σ δϕh = ( δ δ ) ϕh, ϕh 4. Results of measurements (0) 4.. Total harmonc dstorton Fg. 3 shows the changes n the total harmonc dstorton (THD) n the measurement perod. Whle we can observe a hgh complance of the results of measurements carred out usng the dvder and nductve voltage measurng transformer, the measurements performed wth the capactve measurng transformer have much hgher values of THD. δt HD [%] Tab. shows the average values and standard devatons of errors n THD factor measurements carred out by voltage measurng transformers. Measured quantty tme [dd-mm-yy/hh:mm] Indctve voltage transformer Measurng transducer Fg. 4. Errors n voltage THD measurements n the measurement perod 5.0 Resstve voltage dvder δ THD [%] σ δthd [%] tme [dd -mm-yy/hh:mm] Tab.. Average values and standard devatons of errors n THD factor measurements 4.. Voltage harmoncs Fg. 5 shows the frequency spectrum and average values (shares) of voltage harmoncs recorded n the measurement perod. Fg. 3. Changes n voltage THD n the measurement perod The average values and standard devatons of THD measured usng respectve measurng transducers are lsted n Tab.. Measured quantty Resstve voltage dvder Measurng transducer Inductve voltage transformer Capactve voltage transformer U h [%] Resstve voltage dvder THD [%] σ THD [%] HARMOIC UMBER [-] Tab.. Average values and standard devatons of total harmonc dstorton (THD) Fg. 5. The average values of voltage harmoncs n the measurement perod Changes n errors n THD measurements carred out by voltage measurng transformers are shown n Fg. 4. 9

4 R. Pawełek et al. Acta Energetca /9 (04) 7 34 The average values and standard devatons of selected voltage harmoncs domnant n the frequency spectrum are compared n Tab Resstve voltage dvder wh no. Resstve voltage dvder Inductve voltage transformer Capactve voltage transformer U [%] 0. U h% δ Uh% U h% δ Uh% U h% δ Uh% tme [dd-mm-yy/hh: mm] Fg. 7. Changes n the second voltage harmonc Resstve voltage dvder Tab. 3. The average values of voltage harmoncs U 3 [%] For comparson, Fg. 6 shows the maxmum (0-mnute) voltage harmoncs recorded n the measurement perod. The followng fgures (7 0) show the changes n values of selected: (even), 3 (order 3n; zero sequence), 5 (odd, order 3n-; negatve sequence) and 7 (odd, order 3n+; postve sequence) voltage harmoncs recorded n the measurement perod usng varous measurng transducers. Sgnfcant dfferences may be noted only for the second harmonc, where the values measured usng the resstve dvder are much hgher than n the case of voltage measurng transformers. Tab. 4 shows the average values and standard devatons of errors n measurements of selected voltage harmoncs. tme [dd-mm-yy/hh: mm] Fg. 8. Changes n the thrd voltage harmonc Resstve voltage dvder U 5 [%] Uh [%] Resstve voltage dvdre tme [dd-mm-yy/hh: mm] Fg. 9. Changes n the ffth voltage harmonc HARMOIC UMBER [-] Fg. 6. The maxmum values of voltage harmoncs 30

5 R. Pawełek et al. Acta Energetca /9 (04) 7 34 r wh δ UH% σ δuh% δ Uh% σ δuh% Φ U [ o ] Resstve voltage dvder tme [dd-mm-yy/hh: mm] Tab. 4. Errors n measurements of voltage harmoncs usng measurng transformers The lowest values of errors n measurements of voltage harmoncs usng measurng transformers occurred for harmoncs 5 and 7,.e. the harmoncs wth the hghest values. Hgh error values for the other harmoncs (especally even harmoncs) may result from ther low values (less than 0.%), nsgnfcant from the pont of vew of voltage dstorton. Fg. shows the changes n errors n measurement of the ffth harmonc. δu5 [%] tme [dd-mm-yy/hh: mm] Fg.. Changes n errors n measurement of the ffth voltage harmonc 4.3. Phase angles of voltage harmoncs The average values and standard devatons of angles of selected voltage harmoncs are compared n Tab. 5. Fg. shows the changes n phase angles for the fundamental voltage harmonc (n the case of the measurement carred out usng the resstve dvder the phase angle s constant and equal to zero), whereas Fg. 3 llustrates the changes n phase angles for the ffth harmonc. Fg.. Changes n phase angles of fundamental voltage harmonc n the measurement perod wh no. Resstve voltage dvder Inductve voltage transformer Capactve voltage transformer φ h [º] σ φh [º] φ h [º] σ φh [º] φ h [º] σ φh [º] ,6 57,64 5,45 63,464 49,79 37,630 Tab. 5. The average values of phase angles of selected voltage harmoncs Φ U [ o ] Resstve voltage dvder tme [dd-mm-yy/hh: mm] Fg. 3. Changes n phase angles of the ffth voltage harmonc n the measurement perod Fg. shows that n the case of the fundamental voltage harmonc there are also dfferences n phase angles measurements carred out usng the measurng transformers. 3

6 R. Pawełek et al. Acta Energetca /9 (04) 7 34 Tab. 6 shows the average values and standard devatons of errors n measurements of harmonc phase angles. wh no. ϕh δ [º] σ δφh% [º] δ ϕh [º] σ δφh% [º] Tab. 6. Errors n measurements of phase angles of selected voltage harmoncs δ φ [ o ] tme [dd-mm-yy/hh: mm] Fg. 4. Changes n errors n measurements of phase angles for the fundamental voltage harmonc The lowest errors n phase angles measurements were observed for the fundamental voltage harmonc and for the ffth harmonc. Relatvely large errors occurred for the seventh harmonc. Fg. 4 and 5 show the changes n errors n phase angles measurements for the fundamental and ffth harmonc, respectvely. δ Φ [ o ] tme [dd-mm-yy/hh: mm] δ φ [ o ] - - Fg. 5. Changes n errors n measurements of phase angles of the ffth voltage harmonc n the measurement perod tme [dd-mm-yy/hh: mm] Fg. 4. Changes n errors n measurements of phase angles for the fundamental voltage harmonc 4.4. DC voltage component The transfer of DC voltage component by measurng transducers requres a separate analyss. Fg. 6 shows the values of DC component measured n the measurement perod usng respectve measurng transducers. 3

7 R. Pawełek et al. Acta Energetca /9 (04) 7 34 U 0 [%] tme [dd-mm-yy/hh: mm] Fg. 6. Changes n the DC voltage component Resstve voltage dvder DC component wth practcally constant values was recorded n measurements usng the voltage measurng transformers; however, the values dffered sgnfcantly between the nductve and capactve measurng transformers. In the measurements usng the resstve dvder the values of DC component were changng over tme. 5. Summary The voltage dvder was made by Transformex as a result of mplementaton of the development project Desgn and constructon of resstve voltage dvder for measurements of voltage harmoncs n a network of 400 kv ordered and funded by PSE SA (agreement: IF/RB/IF/0/TK/008). The results of voltage harmonc measurements were analysed by the Insttute of Electrcal Power Engneerng at the Lodz Unversty of Technology under the research project Voltage harmonc measurements n a network of 400 kv ordered by PSE SA (agreement: DS/RB/DE/8/TK/0). The results of research are owned by PSE SA. Installaton of the resstve dvder made t possble to carry out comparatve measurements of voltage harmoncs n the network of 400 kv usng nductve and capactve measurng transformers, and the dvder. The measurements were used to estmate the errors occurrng n measurements of values and phase angles of voltage harmoncs carred out wth the use of conventonal measurng transformers. The followng were observed: a hgh complance of the THD values measured wth the use of the dvder and nductve measurng transformer (the average measurement error of 4.5%), and a relatvely hgh value (4.96%) of the average error of measurements carred out usng the capactve measurng transformer. The best accuracy for harmonc measurements carred out usng measurng transformers was obtaned for the ffth and seventh harmoncs, domnant n the voltage frequency spectrum. A sgnfcantly lower accuracy was found n measurement of harmoncs wth shares of less than 0.%. The results suggest that odd and even harmoncs should be treated separately. In measurements of phase angles of voltage harmoncs satsfactory accuracy whle usng nstrument transformer was obtaned only for the fundamental and ffth harmonc. For other harmoncs the errors are relatvely large and characterzed by hgh varablty of values. A separate ssue s a completely dfferent nature of transfer of the DC voltage component by voltage measurng transformers and the resstve dvder. For measurng transformers those values are practcally constant over tme, but vary dependng on the type of transformer, whereas the value of DC component n the case of dvder changes over tme. Although the measurement results obtaned n the course of a one-week sesson are unque n the world, they may not be used as a bass for general conclusons. However, they ndcate problems that should be explaned n further research. More general conclusons can be drawn once the measurements are carred out n a longer tme. References. Meńsk R., Pawełek R., Wasak I., On the eed to Control Power Qualty n Polsh Electrcal etworks, Electrcal Power Qualty and Utlsaton 999, Vol. 5, o., pp. 7.. Błajszczak G., Olak J., Rezystancyjny dzelnk napęca do pomarów wyższych harmoncznych w secach 400 kv [Resstve Voltage Dvder for Hgher Harmoncs Measurement n 400 kv etworks], conference Aktualne problemy w elektroenergetyce (APE ), Jurata, 8 0 June 0, pp Błajszczak G, Resstve Voltage Dvder for Hgher Harmoncs Measurement n 400 kv etwork, IEEE th Internatonal Conference on Electrcal Power Qualty and Utlsaton (EPQU 0), Lsbon (Portugal), 7 9 October 0, pp

8 R. Pawełek et al. Acta Energetca /9 (04) 7 34 Ryszard Pawełek Lodz Unversty of Technology e-mal: ryszard.pawelek@p.lodz.pl Graduated from the Faculty of Electrcal Engneerng at Lodz Unversty of Technology (977). He s currently employed at the Insttute of Electrcal Power Engneerng at hs home unversty as a lecturer, where he works as the Deputy Drector of the Insttute. Hs scentfc nterests nclude: qualty of electrcty, dstrbuted electrcty generaton, power mcro-systems. He s a member of The Polsh Commttee for Qualty and Effcent Use of Electrcty, n whch he acts as Vce-Presdent for Scence. Expert of the Polsh Assocaton of Electrcal Engneers (SEP) n the feld of electrcty qualty. Irena Wasak Lodz Unversty of Technology e-mal: rena.wasak@p.lodz.pl She graduated from Lodz Unversty of Technology. Snce the begnnng of her career she has been workng at the Insttute of Electrcal Power Engneerng. She obtaned doctoral and postdoctoral degrees n the feld of electrcal power engneerng. In she was Vce Dean of the Faculty of Electrcal, Electronc, Computer and Control Engneerng at Lodz Unversty of Technology. She currently s the Drector of the Insttute and Head of the Department of Electrcal Power etworks. She s also a member of The Insttuton of Engneerng and Technology and The Polsh Commttee for Qualty and Effcent Use of Electrcty, The Polsh Assocaton of Electrcal Engneers (SEP), and an assocate member of the Electrcal Power Systems Secton at the Polsh Academy of Scences (PA). She s the deputy edtor of the journal Electrcal Power Qualty and Utlsaton and the co-presdent of the nternatonal conference wth the same name. Her scentfc actvtes nclude the ssues of power qualty, ntegraton of dstrbuted energy sources n power networks, operaton of power mcro-systems. Maran Jurek Polske Sec Elektroenergetyczne SA e-mal: pawel.kelm@p.lodz.pl In he was employed n Polske Sec Elektroenergetyczne (Polsh Power Grd), currently PSE Operator SA, where he handled system servces, then nternatonal energy exchange settlement. ow he s responsble for mplementaton of new technologes, energy qualty and reactve power management. Snce February 0 he has mplemented a half-year project on the power plant control systems n Emerson Process Management Power & Water Solutons. He currently collaborates wth Cty Energy sp. z o.o. A member of the followng: The Polsh Assocaton of Electrcal Engneers (SEP), IEEE, Eurelectrc, The Scentfc and Techncal (OT) Commttee for Energy Management and The Polsh Commttee for Qualty and Effcent Use of Electrcty. An expert n electrcty qualty, and author of over 0 scentfc and techncal publcatons. 34

9 R. Pawełek et al. Acta Energetca /9 (04) translaton 7 34 Ths s a supportng translaton of the orgnal text publshed n ths ssue of Acta Energetca on pages When referrng to the artcle please refer to the orgnal text. Pomary wyższych harmoncznych napęca w sec 400 kv PL Autorzy Ryszard Pawełek Irena Wasak Maran Jurek Słowa kluczowe wyższe harmonczne, jakość energ elektrycznej, pomary jakośc energ elektrycznej Streszczene W artykule przedstawono analzę wynków pomarów wyższych harmoncznych napęca, wykonanych w sec przesyłowej 400 kv. Sygnały pomarowe napęć uzyskano z trzech przetwornków pomarowych: rezystancyjnego dzelnka napęca, napęcowego przekładnka ndukcyjnego oraz napęcowego przekładnka pojemnoścowego. Wynk pomarów z dzelnka rezystancyjnego przyjęto jako referencyjne, odnosząc do nch wynk pomarów uzyskane przy wykorzystanu przekładnków. Dokonano oszacowana błędów pomarowych wyższych harmoncznych napęca powodowanych przez przekładnk.. Wprowadzene ajczęścej do pomaru wyższych harmoncznych w secach najwyższych napęć wykorzystywane są transformatory pomarowe (przekładnk napęcowe). Przekładnk napęcowe różnych typów stosowane w energetyce projektowane są do pracy przy częstotlwośc 50 Hz, a ch charakterystyk przenoszena dla wyższych częstotlwośc ne są znane. Analzując schematy zastępcze przekładnków, należy zauważyć wpływ ndukcyjnośc, pojemnośc lcznych nelnowośc na ch charakterystyk przenoszena w dzedzne częstotlwośc. Potrzeba montorowana parametrów jakośc energ elektrycznej w secach elektroenergetycznych od dawna była sygnalzowana []. Chcąc wykonać dokładny pomar wyższych harmoncznych (wh) napęca, częstotlwośc oraz pojedynczych zakłóceń (np. stromośc przepęć lub zapadów), operator sec przesyłowej PSE Operator SA, przy współpracy z frmą Transformex sp. z o.o., zanstalował w jednej ze stacj 400 kv pomarowy dzelnk rezystancyjny. Szczegółowy ops technczny dzelnka został zameszczony w [, 3]. Dzelnk rezystancyjny z założena pownen być elementem lnowym w dzedzne częstotlwośc w zwązku z tym przenosć przebeg chwlowe napęca w stanach przejścowych ustalonych pracy sec bez żadnych znekształceń. Pownen być węc pozbawony wększośc wad, które mają przekładnk napęcowe. Własnośc pomarowe dzelnka w tym zakrese zostały potwerdzone badanam laboratoryjnym, wykonanym przez Instytut Elektrotechnk (Warszawa-Mędzylese) []. Dzelnk rezystancyjny wykorzystano do porównana oceny wynków pomarów harmoncznych napęca pomerzonych, przy wykorzystanu wybranych typów przekładnków napęcowych wysokego napęca. a podstawe pomarów porównawczych będze można określć przydatność przekładnków napęcowych do pomarów wyższych harmoncznych, a w nektórych przypadkach określć współczynnk korekcyjne.. Wykonane pomarów Pomary wyższych harmoncznych w sec 400 kv wykonane zostały przy użycu analzatora typu UP-0 produkcj szwedzkej frmy Unpower. a trzy nezależne wejśca napęcowe analzatora zostały wprowadzone jednocześne sygnały pomarowe tego samego napęca fazowego, pochodzące z: rezystancyjnego dzelnka napęca, napęcowego przekładnka ndukcyjnego oraz napęcowego przekładnka pojemnoścowego. Pomary były wykonywane przez 7 dn ( grudna 0, godz. 9 grudna 0, godz. ). Poszczególne welkośc merzone były w sposób cągły (co pół okresu krzywej napęca) uśrednane w przedzałach 0-mnutowych. Merzone były wartośc napęca fazowego, wartośc współczynnków odkształcena napęca, wartośc względne (procentowe) poszczególnych harmoncznych ch kąty fazowe. Wynk pomarów, uzyskane z wykorzystanem dzelnka rezystancyjnego o charakterystyce przenoszena nezależnej od częstotlwośc, przyjęto jako referencyjne, odnosząc do nch wynk pomarów uzyskane przy wykorzystanu przekładnków. Kąty fazowe poszczególnych harmoncznych wyznaczane były względem kąta fazowego podstawowej harmoncznej napęca merzonego przy wykorzystanu dzelnka rezystancyjnego (φ U(d) = 0 ). Pole 400 kv, w którym zanstalowany jest dzelnk rezystancyjny, jest załączane okresowo, dlatego lczebność próbek dla poszczególnych merzonych welkośc wynos 494 w okrese tygodnowym (zamast 008). a rys. pokazano zmany wartośc skutecznej napęca fazowego, merzonego w okresach załączena dzelnka. U [kv] czas [dd-mm-rr/gg:mm] Rys.. Zmany napęca dzelnka w okrese pomarowym a rys. przedstawono zmany wartośc skutecznej napęca merzonego przy wykorzystanu wszystkch trzech przetwornków pomarowych. U [kv] Rys.. Zmany napęca w okrese pomarowym 3. Metoda oceny wynków pomarów Ocenę dokładnośc pomaru wyższych harmoncznych ch kątów fazowych przez przekładnk napęcowe przeprowadzono według następującej procedury:. Ze zborów względnych wartośc wyższych harmoncznych, zmerzonych przy wykorzystanu poszczególnych przetwornków (rezystancyjnego dzelnka napęca, napęcowego przekładnka ndukcyjnego oraz napęcowego przekładnka pojemnoścowego), wyznaczono wartośc średne: U h%, U h = () % gdze: U h%, wartość względna h-tej harmoncznej w -tym przedzale 0-mnutowym, = 494 lczba pomarów oraz określono odchylene standardowe: czas [dd-mm-rr/gg:mm] ( U U ) h%, h% Dzelnk rezystancyjny () σuh% =. Analogczne ze zborów wartośc kątów fazowych harmoncznych, zmerzonych przy wykorzystanu poszczególnych przetwornków, wyznaczono wartośc średne: 35

10 R. Pawełek et al. Acta Energetca /9 (04) translaton 7 34 ϕh, (3) ϕh = gdze: φ h, wartość kąta fazowego h-tej harmoncznej w -tym przedzale 0-mnutowym oraz określono odchylene standardowe: ( ϕh, ϕh) (4) σ ϕ h = Dla poszczególnych harmoncznych napęca uzyskanych przy wykorzystanu przekładnków napęcowych (ndukcyjnego bądź pojemnoścowego) wyznaczono błąd względny, przyjmując jako wartość referencyjną wynk pomaru uzyskany za pomocą dzelnka rezystancyjnego: U h%, ( p) U h%, ( d ) δ Uh%, = 00% (5) U h%, ( d ) gdze: U h%,(p) wartość względna h-tej harmoncznej w -tym przedzale 0-mnutowym, zmerzona przy wykorzystanu przekładnka napęcowego, U h%,(d) wartość względna h-tej harmoncznej w -tym przedzale 0-mnutowym, zmerzona przy wykorzystanu dzelnka rezystancyjnego, a następne wyznaczono wartość średną odchylene standardowe dla tego błędu, zgodne z zależnoścam (6) (7): δuh%, δ Uh% = (6) = ( δ δ ) Uh%, Uh% σ δ Uh% (7) W analogczny sposób wyznaczono błąd kątowy dla pomarów poszczególnych harmoncznych napęca uzyskanych przy wykorzystanu przekładnków napęcowych (ndukcyjnego bądź pojemnoścowego): δ ϕ h, ϕh, ( p) ϕh, ( d ) = (8) gdze: φ h,(p) wartość kąta fazowego h-tej harmoncznej w -tym przedzale 0-mnutowym, zmerzona przy wykorzystanu przekładnka napęcowego, φ h,(d) wartość kąta fazowego h-tej harmoncznej w -tym przedzale 0-mnutowym, zmerzona przy wykorzystanu dzelnka rezystancyjnego, oraz wyznaczono wartość średną odchylene standardowe dla tego błędu, zgodne z zależnoścam (9) (0): δ δϕh, ϕh = = ( δ δ ) ϕh, ϕh (9) σ δϕh (0) 4. Wynk pomarów 4.. Całkowty współczynnk odkształcena napęca a rys. 3 pokazano zmany wartośc całkowtego współczynnka odkształcena napęca (THD) w okrese pomarowym. O le można zauważyć dużą zgodność wynków pomarów wykonanych przy wykorzystanu dzelnka przekładnka ndukcyjnego, o tyle pomary dokonane za pomocą przekładnka pojemnoścowego 5.0 THD [%] Dzelnk rezystancyjny czas [dd-mm-rr/gg:mm] Rys. 3. Zmany wartośc THD napęca w okrese pomarowym Welkość merzona THD Dzelnk rezystancyjny dają znaczne wększe wartośc współczynnka THD. Wartośc średne oraz odchylena standardowe współczynnka THD, zmerzone za pomocą poszczególnych przetwornków pomarowych, zestawono w tab.. Zmany wartośc błędów pomaru współczynnka THD przez przekładnk napęcowe pokazano na rys. 4. Przetwornk pomarowy Przekładnk pojemnoścowy [%],80,73,0 σ THD [%] 0,59 0,59 0,79 Tab.. Wartośc średne odchylena standardowe całkowtego współczynnka odkształcena napęca THD Welkość merzona -3 Przetwornk pomarowy δ THD [%] 4,50 4,96 σ δthd [%],9 6,03 Rys. 4. Błędy pomarowe THD napęca w okrese pomarowym Tab.. Wartośc średne odchylena standardowe błędów pomaru współczynnka THD r wh δ T HD [%] Dzelnk rezystancyjny U h% σ Uh% U h% σ Uh% U h% σ Uh% 0,67 0,005 0,05 0,005 0,0 0, ,96 0,040 0,5 0,037 0,73 0, ,075 0,0 0,0 0,009 0,05 0,009 5,98 0,3,66 0,3,30 0, ,057 0,04 0,06 0,03 0,03 0,05 7,54 0,66,098 0,659,49 0, ,055 0,05 0,047 0,0 0,5 0,073 0,45 0,3 0,48 0, 0,6 0, ,04 0,0 0,039 0,00 0,037 0,05 Tab. 3. Wartośc średne wyższych harmoncznych napęca 36

11 R. Pawełek et al. Acta Energetca /9 (04) translaton 7 34 W tab. podano średne wartośc odchylena standardowe błędów pomaru współczynnka THD przez przekładnk napęcowe. 4.. Wyższe harmonczne napęca a rys. 5 pokazano spektrum częstotlwoścowe (wdmo) wartośc średne (udzały) wyższych harmoncznych zarejestrowanych w okrese pomarowym. Wartośc średne odchylena standardowe wybranych domnujących w wdme częstotlwoścowym harmoncznych napęca, zestawono w tab. 3. r wh U h [%] Dzelnk rezystancyjny UMER HARMOICZEJ [-] Rys. 5. Wartośc średne wyższych harmoncznych napęca w okrese pomarowym δ Uh% σ δuh% δ Uh% σ δuh% 85,5,94 86,6 3,44 3,60 4,,43 8,47 4 8,59 0,85 78,36,7 5 3,00,97 9,, ,6,08 47,50 3,30 7 6,30 3,34 7,8 5,60 9 5,34 5,87 3,05,50 0,93,58 33,7 8, 3 4,77,80 6,4 5,89 Tab. 4. Błędy pomaru wyższych harmoncznych napęca za pomocą przekładnków r wh Dzelnk rezystancyjny φ h [º] σ φh [º] φ h [º] σ φh [º] φ h [º] σ φh [º] 0,000 0,000 0,0 0, Dla porównana na rys. 6 pokazano wartośc maksymalne (0-mnutowe) wyższych harmoncznych zarejestrowane w okrese pomarowym. a kolejnych rysunkach (7 0) przedstawono zmany wartośc wybranych: (parzysta), 3 (rzędu 3n; kolejność zerowa), 5 (neparzysta rzędu 3n ; kolejność przecwna) 7 (neparzysta rzędu 3n+; kolejność zgodna) wyższych harmoncznych napęca, zarejestrowane w okrese pomarowym przy wykorzystanu różnych przetwornków pomarowych. Istotne różnce można zauważyć tylko w przypadku drugej harmoncznej, gdze wartośc zmerzone przy zastosowanu dzelnka rezystancyjnego są zdecydowane wyższe nż przy wykorzystanu przekładnków. W tab. 4 podano średne wartośc odchylena standardowe błędów pomaru, przeprowadzonego za pomocą przekładnków napęcowych, wybranych wyższych harmoncznych. Uh [%] Dzelnk rezystancyjny UMER HARMOICZEJ [-] Rys. 6. Wartośc maksymalne wyższych harmoncznych napęca 0.3 Dzelnk rezystancyjny 87,44 0,79 6,5 5,497 98,495 5,95 3 3,85 6,863 4,984 4,05 4,858, ,978 7,4 84,640 65,79 09,467 69, ,967 4,866 6,057 4,59 3,33 4,79 6 0,06 7,476 8,87 37,989 3,36 5,879 U [%] ,87 58,503,843 58,863 7,3 58, ,585 3,70 4,69 7,09 4,43 3,889 4,67,034,403,404 06,55 0,776 Rys. 7. Zmany wartośc drugej harmoncznej napęca 3,6 57,64 5,45 63,464 49,79 37, Dzelnk rezystancyjny Tab. 5. Wartośc średne kątów fazowych wybranych harmoncznych napęca U 3 [%] r wh δ φh [º] Przekładnk ndukcyjny σ δφh% [º] δ φh [º] Przekładnk pojemnoścowy σ δφh% [º] 0,0 0,57 0,37 0,56 5,6 5,0,08 4, ,33 9,877 9,007 8, ,68 67,50 00,446 7, ,090 0,966,644,8 6 7,6 34,909,74 49,50 7 4,30 98,67 4,56 77,40 9 3,36 55,459 59,558 49,856 8,36 0,758 0,79 0, ,96 30,377 6,35 7,447 Tab. 6. Błędy pomarów kątów fazowych wybranych harmoncznych napęca Rys. 8. Zmany wartośc trzecej harmoncznej napęca U 5 [%] Dzelnk rezystancyjny Rys. 9. Zmany wartośc pątej harmoncznej napęca 37

12 R. Pawełek et al. Acta Energetca /9 (04) translaton 7 34 Dzelnk rezystancyjny r wh Przekładnk ndukcyjny Przekładnk pojemnoścowy δ φh [º] σ δφh% [º] δ φh [º] σ δφh% [º] Uh [%] Rys. 0. Zmany wartośc sódmej harmoncznej napęca ajmnejsze wartośc błędów pomaru wyższych harmoncznych za pomocą przekładnków wystąpły dla harmoncznych 5 7, czyl dla harmoncznych o najwększych wartoścach. Duże wartośc błędów dla pozostałych harmoncznych (szczególne harmoncznych parzystych) mogą wynkać z ch małych wartośc (ponżej 0,%), nestotnych z punktu wdzena odkształcena przebegu napęca. a rys. pokazano zmany wartośc błędów pomaru wartośc pątej harmoncznej. 0,0 0,57 0,37 0,56 5,6 5,0,08 4, ,33 9,877 9,007 8, ,68 67,50 00,446 7, ,090 0,966,644,8 6 7,6 34,909,74 49,50 7 4,30 98,67 4,56 77,40 9 3,36 55,459 59,558 49,856 8,36 0,758 0,79 0, ,96 30,377 6,35 7,447 Tab. 6. Błędy pomarów kątów fazowych wybranych harmoncznych napęca? U5 [ o ] 8 Dzelnk rezystancyjny ?? 5 [ o ] ?U5 [%] Rys.. Zmany wartośc błędów pomaru pątej harmoncznej napęca 4.3. Kąty fazowe harmonczne napęca Wartośc średne odchylena standardowe kątów wybranych harmoncznych napęca zestawono w tab. 5. a rys. pokazano zmany kątów fazowych dla podstawowej harmoncznej napęca (w przypadku pomaru z wykorzystanem dzelnka rezystancyjnego kąt fazowy jest stały równy zeru), a na rys. 3 zmany kątów fazowych dla pątej harmoncznej.? U [ o ] Dzelnk rezystancyjny Rys.. Zmany wartośc kątów fazowych harmoncznej podstawowej napęca w okrese pomarowym Rys. 3. Zmany wartośc kątów fazowych pątej harmoncznej napęca w okrese pomarowym Z rys. wynka, że także w przypadku harmoncznej podstawowej występują różnce kątów fazowych przy pomarach z wykorzystanem przekładnków. W tab. 6 podano średne wartośc odchylena standardowe błędów pomaru kątów fazowych harmoncznych za pomocą przekładnków napęcowych. ajmnejsze błędy pomarów kątów fazowych zaobserwowano dla harmoncznej podstawowej dla harmoncznej pątej. atomast stosunkowo duże błędy wystąpły dla sódmej harmoncznej. a rys. 4 5 pokazano zmany wartośc błędów pomaru wartośc kątów fazowych odpowedno dla podstawowej pątej harmoncznej.?? [ o ] Rys. 4. Zmany wartośc błędów pomarowych kątów fazowych harmoncznej podstawowej napęca Rys. 5. Zmany wartośc błędów pomarowych kątów fazowych pątej harmoncznej napęca w okrese pomarowym 4.4. Składowa stała napęca Oddzelnego potraktowana wymaga problem przenoszena przez przetwornk pomarowe składowej stałej napęca. a rys. 6 pokazano zmany wartośc składowej stałej, zmerzone w okrese pomarowym za pomocą poszczególnych przetwornków U 0 [%] Dzelnk rezystancyjny Rys. 6. Zmany wartośc składowej stałej napęca pomarowych. Przy pomarach z wykorzystanem przekładnków napęcowych zarejestrowano składową stałą o praktyczne stałych wartoścach, różnących sę jednak znaczne dla przekładnka ndukcyjnego pojemnoścowego. atomast dla pomarów z użycem dzelnka rezystancyjnego składowa stała ma wartośc zmenające sę w czase. 5. Podsumowane Dzelnk napęca został wykonany przez frmę Transformex w wynku realzacj pracy rozwojowej pt. Projekt budowa rezystancyjnego dzelnka napęca do pomarów wyższych harmoncznych napęca w sec 38

13 R. Pawełek et al. Acta Energetca /9 (04) translaton kv, zleconej sfnansowanej przez PSE SA (umowa: IF/RB/IF/0/TK/008). Analza wynków pomarów wyższych napęca została przeprowadzona przez Instytut Elektroenergetyk Poltechnk Łódzkej w wynku realzacj pracy badawczej pt. Pomary wyższych harmoncznych napęca w sec 400 kv, zleconej przez PSE SA (umowa: DS/RB/DE/8/TK/0). Wynk badań stanową własność PSE SA. Zanstalowane dzelnka rezystancyjnego umożlwło wykonane pomarów porównawczych wyższych harmoncznych napęca w sec 400 kv przy zastosowanu przekładnków napęcowych: ndukcyjnego pojemnoścowego oraz dzelnka. a podstawe pomarów oszacowano błędy powstające przy pomarach wartośc kątów fazowych harmoncznych napęca, wykonywanych z wykorzystanem przekładnków. Stwerdzono dużą zgodność wartośc współczynnka THD, pomerzonych przy wykorzystanu dzelnka przekładnka ndukcyjnego (średn błąd pomarów wynosł 4,5%), oraz stosunkowo dużą wartość (4,96%) średnego błędu pomarów wykonanych za pomocą przekładnka pojemnoścowego. ajlepszą dokładność pomaru harmoncznych za pomocą przekładnków uzyskano dla harmoncznej pątej sódmej, domnujących w spektrum częstotlwoścowym napęca. Znaczne mnejszą dokładnoścą charakteryzuje sę pomar harmoncznych o udzałach ponżej 0,%. Wynk sugerują, że w sposób odrębny należy traktować harmonczne neparzyste parzyste. Przy pomarach kątów fazowych wyższych harmoncznych zadowalającą dokładność pomaru za pomocą przekładnków uzyskano tylko dla harmoncznej podstawowej harmoncznej pątej. Dla pozostałych harmoncznych błędy są stosunkowo duże, a poza tym cechuje je duża zmenność wartośc. Oddzelnym problemem jest całkowce różny charakter przenoszena składowej stałej napęca przez przekładnk napęcowe przez dzelnk rezystancyjny. Dla przekładnków są to wartośc praktyczne stałe w czase, ale różne w zależnośc od rodzaju przekładnka, natomast dla dzelnka wartość składowej stałej zmena sę w czase. Wynk pomarów, uzyskane w trakce jednotygodnowej sesj, chocaż unkatowe w skal śwatowej, ne mogą być podstawą do wnosków ogólnych. Sugerują jednak problemy, które należy próbować wyjaśnć w dalszych badanach. Bardzej ogólne wnosk będze można sformułować po wykonanu pomarów w dłuższym czase. Bblografa. Meńsk R., Pawełek R., Wasak I., On the eed to Control Power Qualty n Polsh Electrcal etworks, Electrcal Power Qualty and Utlsaton 999, Vol. 5, o., s. 7.. Błajszczak G., Olak J., Rezystancyjny dzelnk napęca do pomarów wyższych harmoncznych w secach 400 kv, konferencja Aktualne problemy w elektroenergetyce (APE ), Jurata, 8 0 czerwca 0, s Błajszczak G, Resstve Voltage Dvder for Hgher Harmoncs Measurement n 400 kv etwork, IEEE th Internatonal Conference on Electrcal Power Qualty and Utlsaton (EPQU 0), Lsbon (Portugal), 7 9 October 0, s. 4. Ryszard Pawełek dr nż. Poltechnka Łódzka e-mal: ryszard.pawelek@p.lodz.pl Absolwent Wydzału Elektrycznego Poltechnk Łódzkej (977). Obecne jest zatrudnony w Instytuce Elektroenergetyk swojej macerzystej uczeln na stanowsku adunkta, gdze pełn funkcję zastępcy dyrektora Instytutu. Obszar zanteresowań naukowych obejmuje: jakość energ elektrycznej, generację rozproszoną, mkrosystemy elektroenergetyczne. Jest członkem Polskego Komtetu Jakośc Efektywnego Użytkowana Energ Elektrycznej, w którym pełn funkcję wceprzewodnczącego ds. nauk. Rzeczoznawca SEP w dzedzne jakośc energ elektrycznej. Irena Wasak dr hab. nż., prof. nadzw. Poltechnka Łódzka e-mal: rena.wasak@p.lodz.pl Absolwentka Poltechnk Łódzkej. Od początku karery zawodowej pracuje w Instytuce Elektroenergetyk tej uczeln. Uzyskała stopne naukowe doktora doktora habltowanego z dzedzny elektroenergetyk. W latach była prodzekanem Wydzału Elektrotechnk, Elektronk, Informatyk Automatyk PŁ. Obecne pełn funkcję kerownka Zakładu Sec Elektroenergetycznych Mkrosystemów. Członkn The Insttuton of Engneerng and Technology oraz Komtetu ds. Jakośc Efektywnego Użytkowana Energ Elektrycznej SEP, członek stowarzyszony Sekcj Systemów Elektroenergetycznych PA. Pełn funkcję zastępcy redaktora naczelnego czasopsma Electrcal Power Qualty and Utlsaton oraz współprzewodnczącej mędzynarodowej konferencj o tej samej nazwe. Obszar dzałalnośc naukowej obejmuje zagadnena jakośc zaslana, ntegracj rozproszonych źródeł energ w secach elektroenergetycznych, funkcjonowana mkrosystemów elektroenergetycznych. Maran Jurek dr nż. Polske Sec Elektroenergetyczne SA e-mal: pawel.kelm@p.lodz.pl W latach pracował w Polskch Secach Elektroenergetycznych, obecne PSE Operator SA, gdze zajmował sę usługam systemowym, następne rozlczenam mędzynarodowej wymany energ, a w ostatnch latach wdrażanem nowych technolog oraz jakoścą energ zarządzanem mocą berną. Od lutego 0 roku realzował półroczny projekt dotyczący układów sterowana elektrown w Emerson Process Management Power & Water Solutons. Aktualne współpracuje z Cty Energy sp. z o.o. Jest członkem m.n.: SEP, IEEE, Eurelectrc, Komtetu OT ds. Gospodark Energetycznej, Polskego Komtetu Jakośc Efektywnego Użytkowana Energ Elektrycznej. Rzeczoznawca w dzedzne jakośc energ elektrycznej, a także autor ponad 0 publkacj naukowych techncznych. 39

Evaluation of estimation accuracy of correlation functions with use of virtual correlator model

Evaluation of estimation accuracy of correlation functions with use of virtual correlator model Jadwga LAL-JADZIAK Unwersytet Zelonogórsk Instytut etrolog Elektrycznej Elżbeta KAWECKA Unwersytet Zelonogórsk Instytut Informatyk Elektronk Ocena dokładnośc estymacj funkcj korelacyjnych z użycem modelu

Bardziej szczegółowo

WSPOMAGANE KOMPUTEROWO POMIARY CZĘSTOTLIWOŚCI CHWILOWEJ SYGNAŁÓW IMPULSOWYCH

WSPOMAGANE KOMPUTEROWO POMIARY CZĘSTOTLIWOŚCI CHWILOWEJ SYGNAŁÓW IMPULSOWYCH Metrologa Wspomagana Komputerowo - Zegrze, 9-22 05.997 WSPOMAGANE KOMPUTEROWO POMIARY CZĘSTOTLIWOŚCI CHWILOWEJ SYGNAŁÓW IMPULSOWYCH dr nż. Jan Ryszard Jask, dr nż. Elgusz Pawłowsk POLITECHNIKA lubelska

Bardziej szczegółowo

REZYSTANCYJNY DZIELNIK NAPIĘCIA DO POMIARÓW WYŻSZYCH HARMONICZNYCH W SIECIACH 400 KV

REZYSTANCYJNY DZIELNIK NAPIĘCIA DO POMIARÓW WYŻSZYCH HARMONICZNYCH W SIECIACH 400 KV AKTUALNE PROBLEMY W ELEKTROENERGETYCE JURATA 8 10 CZERWCA 2011 REZYSTANCYJNY DZIELNIK NAPIĘCIA DO POMIARÓW WYŻSZYCH HARMONICZNYCH W SIECIACH 400 KV Grzegorz Błajszczak, PSE Operator S.A. Jan Olak Transformex

Bardziej szczegółowo

LABORATORIUM PODSTAW ELEKTROTECHNIKI Badanie obwodów prądu sinusoidalnie zmiennego

LABORATORIUM PODSTAW ELEKTROTECHNIKI Badanie obwodów prądu sinusoidalnie zmiennego Ćwczene 1 Wydzał Geonżyner, Górnctwa Geolog ABORATORUM PODSTAW EEKTROTECHNK Badane obwodów prądu snusodalne zmennego Opracował: Grzegorz Wśnewsk Zagadnena do przygotowana Ops elementów RC zaslanych prądem

Bardziej szczegółowo

ZESZYTY NAUKOWE INSTYTUTU POJAZDÓW 2(88)/2012

ZESZYTY NAUKOWE INSTYTUTU POJAZDÓW 2(88)/2012 ZESZYTY NAUKOWE INSTYTUTU POJAZDÓW (88)/01 Hubert Sar, Potr Fundowcz 1 WYZNACZANIE ASOWEGO OENTU BEZWŁADNOŚCI WZGLĘDE OSI PIONOWEJ DLA SAOCHODU TYPU VAN NA PODSTAWIE WZORU EPIRYCZNEGO 1. Wstęp asowy moment

Bardziej szczegółowo

Sprawozdanie powinno zawierać:

Sprawozdanie powinno zawierać: Sprawozdane pownno zawerać: 1. wypełnoną stronę tytułową (gotowa do ćw. nr 0 na strone drugej, do pozostałych ćwczeń zameszczona na strone 3), 2. krótk ops celu dośwadczena, 3. krótk ops metody pomaru,

Bardziej szczegółowo

Plan wykładu: Typowe dane. Jednoczynnikowa Analiza wariancji. Zasada: porównać zmienność pomiędzy i wewnątrz grup

Plan wykładu: Typowe dane. Jednoczynnikowa Analiza wariancji. Zasada: porównać zmienność pomiędzy i wewnątrz grup Jednoczynnkowa Analza Waranc (ANOVA) Wykład 11 Przypomnene: wykłady zadana kursu były zaczerpnęte z podręcznków: Statystyka dla studentów kerunków techncznych przyrodnczych, J. Koronack, J. Melnczuk, WNT

Bardziej szczegółowo

HARMONIC REDUCTION TECHNIQUES USING MULTI-PULSE RECTIFIERS

HARMONIC REDUCTION TECHNIQUES USING MULTI-PULSE RECTIFIERS PAWEŁ STAWCZYK Kelce Unversty of Technology e-mal: pawle83@o.pl HARMONIC REDUCTION TECHNIQUES USING MULTI-PULSE RECTIFIERS A b s t r a c t AC/DC converters generate hgh harmonc currents and voltages nto

Bardziej szczegółowo

WPŁYW PARAMETRÓW DYSKRETYZACJI NA NIEPEWNOŚĆ WYNIKÓW POMIARU OBIEKTÓW OBRAZU CYFROWEGO

WPŁYW PARAMETRÓW DYSKRETYZACJI NA NIEPEWNOŚĆ WYNIKÓW POMIARU OBIEKTÓW OBRAZU CYFROWEGO Walenty OWIECZKO WPŁYW PARAMETRÓW DYSKRETYZACJI A IEPEWOŚĆ WYIKÓW POMIARU OBIEKTÓW OBRAZU CYFROWEGO STRESZCZEIE W artykule przedstaono ynk analzy nepenośc pomaru ybranych cech obektu obrazu cyfroego. Wyznaczono

Bardziej szczegółowo

SSW1.1, HFW Fry #20, Zeno #25 Benchmark: Qtr.1. Fry #65, Zeno #67. like

SSW1.1, HFW Fry #20, Zeno #25 Benchmark: Qtr.1. Fry #65, Zeno #67. like SSW1.1, HFW Fry #20, Zeno #25 Benchmark: Qtr.1 I SSW1.1, HFW Fry #65, Zeno #67 Benchmark: Qtr.1 like SSW1.2, HFW Fry #47, Zeno #59 Benchmark: Qtr.1 do SSW1.2, HFW Fry #5, Zeno #4 Benchmark: Qtr.1 to SSW1.2,

Bardziej szczegółowo

Environment Protection Engineering APPLICATION OF BOOT STATISTICAL PACKAGE IN CALCULATING POLLUTANT SPREADING IN AIR

Environment Protection Engineering APPLICATION OF BOOT STATISTICAL PACKAGE IN CALCULATING POLLUTANT SPREADING IN AIR Envronment Protecton Engneerng Vol. 34 2008 No. 4 PRZEMYSŁAW SZCZYGŁOWSKI*, MARIAN MAZUR* APPLICATION OF BOOT STATISTICAL PACKAGE IN CALCULATING POLLUTANT SPREADING IN AIR The ssue of modellng the pollutant

Bardziej szczegółowo

ZESZYTY NAUKOWE INSTYTUTU POJAZDÓW 5(96)/2013

ZESZYTY NAUKOWE INSTYTUTU POJAZDÓW 5(96)/2013 ZESZYTY NAUKOWE NSTYTUTU POJAZDÓW 5(96)/2013 Hubert Sar, Potr Fundowcz 1 WYZNACZANE MASOWEGO MOMENTU BEZWŁADNOŚC WZGLĘDEM OS PODŁUŻNEJ DLA SAMOCHODU TYPU VAN NA PODSTAWE WZORÓW DOŚWADCZALNYCH 1. Wstęp

Bardziej szczegółowo

Pomiar mocy i energii

Pomiar mocy i energii Zakład Napędów Weloźródłowych Instytut Maszyn Roboczych CęŜkch PW Laboratorum Elektrotechnk Elektronk Ćwczene P3 - protokół Pomar mocy energ Data wykonana ćwczena... Zespół wykonujący ćwczene: Nazwsko

Bardziej szczegółowo

APROKSYMACJA QUASIJEDNOSTAJNA

APROKSYMACJA QUASIJEDNOSTAJNA POZNAN UNIVE RSITY OF TE CHNOLOGY ACADE MIC JOURNALS No 73 Electrcal Engneerng 213 Jan PURCZYŃSKI* APROKSYMACJA QUASIJEDNOSTAJNA W pracy wykorzystano metodę aproksymacj średnokwadratowej welomanowej, przy

Bardziej szczegółowo

ANALIZA EKSPLOATACYJNA TRWAŁOŚCI ZESTAWÓW KOŁOWYCH TRAMWAJÓW

ANALIZA EKSPLOATACYJNA TRWAŁOŚCI ZESTAWÓW KOŁOWYCH TRAMWAJÓW TRANSPORT PROBLEMS 202 PROBLEMY TRANSPORTU Volume 7 Issue 2 tram, wheel set, wear, lfe Stansław MŁYNARSKI, Paweł PIEC* Tadeusz Koścuszko Cracow Unversty of Technology, Faculty of Mechancal Engneerng Jana

Bardziej szczegółowo

WYZNACZANIE WSPÓŁCZYNNIKA LEPKOŚCI CIECZY METODĄ STOKESA

WYZNACZANIE WSPÓŁCZYNNIKA LEPKOŚCI CIECZY METODĄ STOKESA WYZNACZANIE WSPÓŁCZYNNIKA LEPKOŚCI CIECZY METODĄ STOKESA. Ops teoretyczny do ćwczena zameszczony jest na strone www.wtc.wat.edu.pl w dzale DYDAKTYKA FIZYKA ĆWICZENIA LABORATORYJNE.. Ops układu pomarowego

Bardziej szczegółowo

POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH

POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH Gliwice, wrzesień 2005 Pomiar napięcia przemiennego Cel ćwiczenia Celem ćwiczenia jest zbadanie dokładności woltomierza cyfrowego dla

Bardziej szczegółowo

MIĘDZYNARODOWE UNORMOWANIA WYRAśANIA ANIA NIEPEWNOŚCI POMIAROWYCH

MIĘDZYNARODOWE UNORMOWANIA WYRAśANIA ANIA NIEPEWNOŚCI POMIAROWYCH MIĘDZYNARODOWE UNORMOWANIA WYRAśANIA ANIA NIEPEWNOŚCI POMIAROWYCH Adam Mchczyńsk W roku 995 grupa nstytucj mędzynarodowych: ISO Internatonal Organzaton for Standardzaton (Mędzynarodowa Organzacja Normalzacyjna),

Bardziej szczegółowo

Teoria niepewności pomiaru (Rachunek niepewności pomiaru) Rodzaje błędów pomiaru

Teoria niepewności pomiaru (Rachunek niepewności pomiaru) Rodzaje błędów pomiaru Pomary fzyczne - dokonywane tylko ze skończoną dokładnoścą. Powodem - nedoskonałość przyrządów pomarowych neprecyzyjność naszych zmysłów borących udzał w obserwacjach. Podawane samego tylko wynku pomaru

Bardziej szczegółowo

± Δ. Podstawowe pojęcia procesu pomiarowego. x rzeczywiste. Określenie jakości poznania rzeczywistości

± Δ. Podstawowe pojęcia procesu pomiarowego. x rzeczywiste. Określenie jakości poznania rzeczywistości Podstawowe pojęca procesu pomarowego kreślene jakośc poznana rzeczywstośc Δ zmerzone rzeczywste 17 9 Zalety stosowana elektrycznych przyrządów 1/ 1. możlwość budowy czujnków zamenających werne każdą welkość

Bardziej szczegółowo

Patients price acceptance SELECTED FINDINGS

Patients price acceptance SELECTED FINDINGS Patients price acceptance SELECTED FINDINGS October 2015 Summary With growing economy and Poles benefiting from this growth, perception of prices changes - this is also true for pharmaceuticals It may

Bardziej szczegółowo

ZASTOSOWANIE ANALIZY HARMONICZNEJ DO OKREŚLENIA SIŁY I DŁUGOŚCI CYKLI GIEŁDOWYCH

ZASTOSOWANIE ANALIZY HARMONICZNEJ DO OKREŚLENIA SIŁY I DŁUGOŚCI CYKLI GIEŁDOWYCH Grzegorz PRZEKOTA ZESZYTY NAUKOWE WYDZIAŁU NAUK EKONOMICZNYCH ZASTOSOWANIE ANALIZY HARMONICZNEJ DO OKREŚLENIA SIŁY I DŁUGOŚCI CYKLI GIEŁDOWYCH Zarys treśc: W pracy podjęto problem dentyfkacj cykl gełdowych.

Bardziej szczegółowo

Rozpoznawanie twarzy metodą PCA Michał Bereta 1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów

Rozpoznawanie twarzy metodą PCA Michał Bereta   1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów Rozpoznawanie twarzy metodą PCA Michał Bereta www.michalbereta.pl 1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów Wiemy, że możemy porównywad klasyfikatory np. za pomocą kroswalidacji.

Bardziej szczegółowo

OpenPoland.net API Documentation

OpenPoland.net API Documentation OpenPoland.net API Documentation Release 1.0 Michał Gryczka July 11, 2014 Contents 1 REST API tokens: 3 1.1 How to get a token............................................ 3 2 REST API : search for assets

Bardziej szczegółowo

BADANIA CHARAKTERYSTYK HYDRAULICZNYCH KSZTAŁTEK WENTYLACYJNYCH

BADANIA CHARAKTERYSTYK HYDRAULICZNYCH KSZTAŁTEK WENTYLACYJNYCH INSTYTUT KLIMATYZACJI I OGRZEWNICTWA ĆWICZENIA LABORATORYJNE Z WENTYLACJI I KLIMATYZACJI: BADANIA CHARAKTERYSTYK HYDRAULICZNYCH KSZTAŁTEK WENTYLACYJNYCH 1. WSTĘP Stanowsko laboratoryjne pośwęcone badanu

Bardziej szczegółowo

ZESZYTY NAUKOWE NR x(xx) AKADEMII MORSKIEJ W SZCZECINIE. Metody wymiarowania obszaru manewrowego statku oparte na badaniach rzeczywistych

ZESZYTY NAUKOWE NR x(xx) AKADEMII MORSKIEJ W SZCZECINIE. Metody wymiarowania obszaru manewrowego statku oparte na badaniach rzeczywistych ISSN 009-069 ZESZYTY NUKOWE NR () KDEMII MORSKIEJ W SZCZECINIE IV MIĘDZYNRODOW KONFERENCJ NUKOWO-TECHNICZN E X P L O - S H I P 0 0 6 Paweł Zalewsk, Jakub Montewka Metody wymarowana obszaru manewrowego

Bardziej szczegółowo

Cracow University of Economics Poland. Overview. Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005

Cracow University of Economics Poland. Overview. Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005 Cracow University of Economics Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005 - Key Note Speech - Presented by: Dr. David Clowes The Growth Research Unit CE Europe

Bardziej szczegółowo

Wyznaczanie współczynnika sztywności zastępczej układu sprężyn

Wyznaczanie współczynnika sztywności zastępczej układu sprężyn Wyznaczane zastępczej sprężyn Ćwczene nr 10 Wprowadzene W przypadku klku sprężyn ze sobą połączonych, można mu przypsać tzw. współczynnk zastępczej k z. W skrajnych przypadkach sprężyny mogą być ze sobą

Bardziej szczegółowo

TRANZYSTOR BIPOLARNY CHARAKTERYSTYKI STATYCZNE

TRANZYSTOR BIPOLARNY CHARAKTERYSTYKI STATYCZNE POLITHNIKA RZSZOWSKA Katedra Podstaw lektronk Instrkcja Nr4 F 00/003 sem. letn TRANZYSTOR IPOLARNY HARAKTRYSTYKI STATYZN elem ćwczena jest pomar charakterystyk statycznych tranzystora bpolarnego npn lb

Bardziej szczegółowo

OKREŚLENIE CZASU MIESZANIA WIELOSKŁADNIKOWEGO UKŁADU ZIARNISTEGO PODCZAS MIESZANIA Z RECYRKULACJĄ SKŁADNIKÓW

OKREŚLENIE CZASU MIESZANIA WIELOSKŁADNIKOWEGO UKŁADU ZIARNISTEGO PODCZAS MIESZANIA Z RECYRKULACJĄ SKŁADNIKÓW Inżynera Rolncza 8(96)/2007 OKREŚLENIE CZASU MIESZANIA WIELOSKŁADNIKOWEGO UKŁADU ZIARNISTEGO PODCZAS MIESZANIA Z RECYRKULACJĄ SKŁADNIKÓW Jolanta Królczyk, Marek Tukendorf Katedra Technk Rolnczej Leśnej,

Bardziej szczegółowo

Praca podkładu kolejowego jako konstrukcji o zmiennym przekroju poprzecznym zagadnienie ekwiwalentnego przekroju

Praca podkładu kolejowego jako konstrukcji o zmiennym przekroju poprzecznym zagadnienie ekwiwalentnego przekroju Praca podkładu kolejowego jako konstrukcj o zmennym przekroju poprzecznym zagadnene ekwwalentnego przekroju Work of a ralway sleeper as a structure wth varable cross-secton - the ssue of an equvalent cross-secton

Bardziej szczegółowo

PRZENOŚNY ANALIZATOR DIAGNOSTYCZNY DO WYKRYWANIA USZKODZEŃ STOJANA I WIRNIKA W SILNIKACH INDUKCYJNYCH

PRZENOŚNY ANALIZATOR DIAGNOSTYCZNY DO WYKRYWANIA USZKODZEŃ STOJANA I WIRNIKA W SILNIKACH INDUKCYJNYCH Zeszyty problemowe Maszyny Elektryczne Nr 00/03 cz. I 77 Marcn Pawlak Poltechnka Wrocławska PRZENOŚNY ANALIZATOR DIAGNOSTYCZNY DO WYKRYWANIA USZKODZEŃ STOJANA I WIRNIKA W SILNIKACH INDUKCYJNYCH PORTABLE

Bardziej szczegółowo

MESHING USING P-METHOD TWORZENIE MODELI DYSKRETNYCH ZA POMOCĄ MODELI TYPU P

MESHING USING P-METHOD TWORZENIE MODELI DYSKRETNYCH ZA POMOCĄ MODELI TYPU P MARTA ŻAKOWSKA MESHING USING P-METHOD TWORZENIE MODELI DYSKRETNYCH ZA POMOCĄ MODELI TYPU P Abstract Accuracy and effcency of analyss carred out thanks to the FEM method manly depends on the qualty of dscrete

Bardziej szczegółowo

Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards

Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards INSPIRE Conference 2010 INSPIRE as a Framework for Cooperation Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards Elżbieta Bielecka Agnieszka Zwirowicz

Bardziej szczegółowo

METHODS FOR MEASUREMENT AND VISUALIZATION OF CHANGES IN BIODIVERSITY

METHODS FOR MEASUREMENT AND VISUALIZATION OF CHANGES IN BIODIVERSITY Proceedngs of ECOpole Vol. 5, No. 20 Marola CHOMCZYŃSKA, Grzegorz ŁAGÓD, Agneszka MONTUSIEWICZ and Jacek MALICKI METHODS FOR MEASUREMENT AND VISUALIZATION OF CHANGES IN BIODIVERSITY METODY POMIARU I WIZUALIZACJI

Bardziej szczegółowo

WPŁYW PRACY LED-OWYCH ŹRÓDEŁ ŚWIATŁA NA PARAMETRY OKREŚLAJĄCE JAKOŚĆ ENERGII ELEK- TRYCZNEJ, CZĘŚĆ 1

WPŁYW PRACY LED-OWYCH ŹRÓDEŁ ŚWIATŁA NA PARAMETRY OKREŚLAJĄCE JAKOŚĆ ENERGII ELEK- TRYCZNEJ, CZĘŚĆ 1 POZNAN UNIVERSITY OF TECHNOLOGY ACADEMIC JOURNALS No 93 Electrcal Engneerng 8 DOI.8/j.897-737.8.93.3 Andrzej LANGE *, Maran PASKO ** WPŁYW PRACY LED-OWYCH ŹRÓDEŁ ŚWIATŁA NA PARAMETRY OKREŚLAJĄCE JAKOŚĆ

Bardziej szczegółowo

Rachunek niepewności pomiaru opracowanie danych pomiarowych

Rachunek niepewności pomiaru opracowanie danych pomiarowych Rachunek nepewnośc pomaru opracowane danych pomarowych Mędzynarodowa Norma Oceny Nepewnośc Pomaru (Gude to Epresson of Uncertanty n Measurements - Mędzynarodowa Organzacja Normalzacyjna ISO) http://physcs.nst./gov/uncertanty

Bardziej szczegółowo

Pomiary parametrów akustycznych wnętrz.

Pomiary parametrów akustycznych wnętrz. Pomary parametrów akustycznych wnętrz. Ocena obektywna wnętrz pod względem akustycznym dokonywana jest na podstawe wartośc następujących parametrów: czasu pogłosu, wczesnego czasu pogłosu ED, wskaźnków

Bardziej szczegółowo

RADIO DISTURBANCE Zakłócenia radioelektryczne

RADIO DISTURBANCE Zakłócenia radioelektryczne AKREDYTOWANE LABORATORIUM BADAWCZE Page (Strona) 2 of (Stron) 9 Following requirements should be taken into account in the case of making use of Test Report and giving information about the tests performed

Bardziej szczegółowo

ASYMETRIA NAPIĘCIOWO - PRĄDOWA W TORZE ZASILANIA PIECA ŁUKOWEGO AC

ASYMETRIA NAPIĘCIOWO - PRĄDOWA W TORZE ZASILANIA PIECA ŁUKOWEGO AC Maszyny Elektryczne - Zeszyty Problemowe Nr /9 () Kazmerz Jageła, Janusz Rak, Marek Gała Poltechnka Częstochowska, Częstochowa, AH, Belsko-Bała ASYMERA NAPĘCOWO - PRĄDOWA W ORZE ZASLANA PECA KOWEGO AC

Bardziej szczegółowo

General Certificate of Education Ordinary Level ADDITIONAL MATHEMATICS 4037/12

General Certificate of Education Ordinary Level ADDITIONAL MATHEMATICS 4037/12 UNIVERSITY OF CAMBRIDGE INTERNATIONAL EXAMINATIONS General Certificate of Education Ordinary Level www.xtremepapers.com *6378719168* ADDITIONAL MATHEMATICS 4037/12 Paper 1 May/June 2013 2 hours Candidates

Bardziej szczegółowo

deep learning for NLP (5 lectures)

deep learning for NLP (5 lectures) TTIC 31210: Advanced Natural Language Processing Kevin Gimpel Spring 2019 Lecture 6: Finish Transformers; Sequence- to- Sequence Modeling and AJenKon 1 Roadmap intro (1 lecture) deep learning for NLP (5

Bardziej szczegółowo

Domy inaczej pomyślane A different type of housing CEZARY SANKOWSKI

Domy inaczej pomyślane A different type of housing CEZARY SANKOWSKI Domy inaczej pomyślane A different type of housing CEZARY SANKOWSKI O tym, dlaczego warto budować pasywnie, komu budownictwo pasywne się opłaca, a kto się go boi, z architektem, Cezarym Sankowskim, rozmawia

Bardziej szczegółowo

WPŁYW ASYMETRII NA WAHANIA NAPIĘCIA W SIECIACH ZASILAJĄCYCH PIECE ŁUKOWE

WPŁYW ASYMETRII NA WAHANIA NAPIĘCIA W SIECIACH ZASILAJĄCYCH PIECE ŁUKOWE OLZYKOWKI Zbgnew wahana napęca, asymetra, pec łukowy WPŁYW YMETRII N WHNI NPIĘI W IEIH ZILJĄYH PIEE ŁKOWE W referace omówono wpływ asymetr na wahana napęca. Przedstawono wynk oblczeń modelowych oraz przebeg

Bardziej szczegółowo

Tychy, plan miasta: Skala 1: (Polish Edition)

Tychy, plan miasta: Skala 1: (Polish Edition) Tychy, plan miasta: Skala 1:20 000 (Polish Edition) Poland) Przedsiebiorstwo Geodezyjno-Kartograficzne (Katowice Click here if your download doesn"t start automatically Tychy, plan miasta: Skala 1:20 000

Bardziej szczegółowo

BADANIE STATYCZNYCH WŁAŚCIWOŚCI PRZETWORNIKÓW POMIAROWYCH

BADANIE STATYCZNYCH WŁAŚCIWOŚCI PRZETWORNIKÓW POMIAROWYCH BADAIE STATYCZYCH WŁAŚCIWOŚCI PRZETWORIKÓW POMIAROWYCH. CEL ĆWICZEIA Celem ćwczena jest poznane: podstawowych pojęć dotyczących statycznych właścwośc przetwornków pomarowych analogowych cyfrowych oraz

Bardziej szczegółowo

Proposal of thesis topic for mgr in. (MSE) programme in Telecommunications and Computer Science

Proposal of thesis topic for mgr in. (MSE) programme in Telecommunications and Computer Science Proposal of thesis topic for mgr in (MSE) programme 1 Topic: Monte Carlo Method used for a prognosis of a selected technological process 2 Supervisor: Dr in Małgorzata Langer 3 Auxiliary supervisor: 4

Bardziej szczegółowo

RADIO DISTURBANCE Zakłócenia radioelektryczne

RADIO DISTURBANCE Zakłócenia radioelektryczne AKREDYTOWANE LABORATORIUM BADAWCZE Page (Strona) 2 of (Stron) 9 Following requirements should be taken into account in the case of making use of Test Report and giving information about the tests performed

Bardziej szczegółowo

Teoria niepewności pomiaru (Rachunek niepewności pomiaru) Rodzaje błędów pomiaru

Teoria niepewności pomiaru (Rachunek niepewności pomiaru) Rodzaje błędów pomiaru Pomary fzyczne - dokonywane tylko ze skończoną dokładnoścą. Powodem - nedoskonałość przyrządów pomarowych neprecyzyjność naszych zmysłów borących udzał w obserwacjach. Podawane samego tylko wynku pomaru

Bardziej szczegółowo

URZĄDZENIE POMIAROWE DO WYZNACZANIA BŁĘDÓW PRZEKŁADNIKÓW PRĄDOWYCH

URZĄDZENIE POMIAROWE DO WYZNACZANIA BŁĘDÓW PRZEKŁADNIKÓW PRĄDOWYCH Prace Naukowe nstytutu Maszyn, Napędów i Pomiarów Elektrycznych Nr 59 Politechniki Wrocławskiej Nr 59 Studia i Materiały Nr 26 2006 Karol NOWAKF *F, Zdzisław NAWROCK * Błędy prądowe i kątowe przekładników

Bardziej szczegółowo

Machine Learning for Data Science (CS4786) Lecture11. Random Projections & Canonical Correlation Analysis

Machine Learning for Data Science (CS4786) Lecture11. Random Projections & Canonical Correlation Analysis Machine Learning for Data Science (CS4786) Lecture11 5 Random Projections & Canonical Correlation Analysis The Tall, THE FAT AND THE UGLY n X d The Tall, THE FAT AND THE UGLY d X > n X d n = n d d The

Bardziej szczegółowo

SPRAWDZANIE PRAWA MALUSA

SPRAWDZANIE PRAWA MALUSA INSTYTUT ELEKTRONIKI I SYSTEMÓW STEROWANIA WYDZIAŁ ELEKTRYCZNY POLITECHNIKA CZĘSTOCHOWSKA LABORATORIUM FIZYKI ĆWICZENIE NR O- SPRAWDZANIE PRAWA MALUSA I. Zagadnena do przestudowana 1. Fala elektromagnetyczna,

Bardziej szczegółowo

SZACOWANIE NIEPEWNOŚCI POMIARU METODĄ PROPAGACJI ROZKŁADÓW

SZACOWANIE NIEPEWNOŚCI POMIARU METODĄ PROPAGACJI ROZKŁADÓW SZACOWANIE NIEPEWNOŚCI POMIARU METODĄ PROPAGACJI ROZKŁADÓW Stefan WÓJTOWICZ, Katarzyna BIERNAT ZAKŁAD METROLOGII I BADAŃ NIENISZCZĄCYCH INSTYTUT ELEKTROTECHNIKI ul. Pożaryskego 8, 04-703 Warszawa tel.

Bardziej szczegółowo

NUMERYCZNO-EKSPERYMENTALNA METODA WYZNACZANIA LOKALNEGO OBCIĄŻENIA CIEPLNEGO ŚCIAN KOMÓR PALENISKOWYCH KOTŁA.

NUMERYCZNO-EKSPERYMENTALNA METODA WYZNACZANIA LOKALNEGO OBCIĄŻENIA CIEPLNEGO ŚCIAN KOMÓR PALENISKOWYCH KOTŁA. PAWEŁ LUDOWSKI NUMERYCZNO-EKSPERYMENTALNA METODA WYZNACZANIA LOKALNEGO OBCIĄŻENIA CIEPLNEGO ŚCIAN KOMÓR PALENISKOWYCH KOTŁA. NUMERICAL-EKSPERIMENTAL METHOD FOR DETERMINING LOCAL HEAT FLUX ABSORBED BY FURNACE

Bardziej szczegółowo

MODELOWANIE PRZEPŁYWU POWIETRZA W KANAŁACH WENTYLACYJNYCH PIECZARKARNI

MODELOWANIE PRZEPŁYWU POWIETRZA W KANAŁACH WENTYLACYJNYCH PIECZARKARNI Inżynera Rolncza 10(108)/2008 MODELOWANIE PRZEPŁYWU POWIETRZA W KANAŁACH WENTYLACYJNYCH PIECZARKARNI Leonard Vorontsov, Ewa Wachowcz Katedra Automatyk, Poltechnka Koszalńska Streszczene: W pracy przedstawono

Bardziej szczegółowo

Few-fermion thermometry

Few-fermion thermometry Few-fermion thermometry Phys. Rev. A 97, 063619 (2018) Tomasz Sowiński Institute of Physics of the Polish Academy of Sciences Co-authors: Marcin Płodzień Rafał Demkowicz-Dobrzański FEW-BODY PROBLEMS FewBody.ifpan.edu.pl

Bardziej szczegółowo

Systemy Ochrony Powietrza Ćwiczenia Laboratoryjne

Systemy Ochrony Powietrza Ćwiczenia Laboratoryjne ś POLITECHNIKA POZNAŃSKA INSTYTUT INŻYNIERII ŚRODOWISKA PROWADZĄCY: mgr nż. Łukasz Amanowcz Systemy Ochrony Powetrza Ćwczena Laboratoryjne 2 TEMAT ĆWICZENIA: Oznaczane lczbowego rozkładu lnowych projekcyjnych

Bardziej szczegółowo

Zasady rejestracji i instrukcja zarządzania kontem użytkownika portalu

Zasady rejestracji i instrukcja zarządzania kontem użytkownika portalu Zasady rejestracji i instrukcja zarządzania kontem użytkownika portalu Rejestracja na Portalu Online Job Application jest całkowicie bezpłatna i składa się z 3 kroków: Krok 1 - Wypełnij poprawnie formularz

Bardziej szczegółowo

WERYFIKACJA EKONOMETRYCZNA MODELU CAPM II RODZAJU DLA RÓŻNYCH HORYZONTÓW STÓP ZWROTU I PORTFELI RYNKOWYCH

WERYFIKACJA EKONOMETRYCZNA MODELU CAPM II RODZAJU DLA RÓŻNYCH HORYZONTÓW STÓP ZWROTU I PORTFELI RYNKOWYCH SCRIPTA COMENIANA LESNENSIA PWSZ m. J. A. Komeńskego w Leszne R o k 0 0 8, n r 6 TOMASZ ŚWIST* WERYFIKACJA EKONOMETRYCZNA MODELU CAPM II RODZAJU DLA RÓŻNYCH HORYZONTÓW STÓP ZWROTU I PORTFELI RYNKOWYCH

Bardziej szczegółowo

Zakopane, plan miasta: Skala ok. 1: = City map (Polish Edition)

Zakopane, plan miasta: Skala ok. 1: = City map (Polish Edition) Zakopane, plan miasta: Skala ok. 1:15 000 = City map (Polish Edition) Click here if your download doesn"t start automatically Zakopane, plan miasta: Skala ok. 1:15 000 = City map (Polish Edition) Zakopane,

Bardziej szczegółowo

Financial support for start-uppres. Where to get money? - Equity. - Credit. - Local Labor Office - Six times the national average wage (22000 zł)

Financial support for start-uppres. Where to get money? - Equity. - Credit. - Local Labor Office - Six times the national average wage (22000 zł) Financial support for start-uppres Where to get money? - Equity - Credit - Local Labor Office - Six times the national average wage (22000 zł) - only for unymployed people - the company must operate minimum

Bardziej szczegółowo

Kształtowanie się firm informatycznych jako nowych elementów struktury przestrzennej przemysłu

Kształtowanie się firm informatycznych jako nowych elementów struktury przestrzennej przemysłu PRACE KOMISJI GEOGRAFII PRZEMY SŁU Nr 7 WARSZAWA KRAKÓW 2004 Akadema Pedagogczna, Kraków Kształtowane sę frm nformatycznych jako nowych elementów struktury przestrzennej przemysłu Postępujący proces rozwoju

Bardziej szczegółowo

03 April 2015 03 kwietnia 2015 r. Zmiana satelity dostarczającego sygnał Animal Planet HD. Change of Delivery Satellite for Animal Planet HD

03 April 2015 03 kwietnia 2015 r. Zmiana satelity dostarczającego sygnał Animal Planet HD. Change of Delivery Satellite for Animal Planet HD 03 April 2015 03 kwietnia 2015 r. Dear Sirs, Change of Delivery Satellite for Animal Planet HD We refer to the Affiliation Agreement with a Commencement Date of 01/11/2009 between ( DCEL / we ) and you,

Bardziej szczegółowo

photo graphic Jan Witkowski Project for exhibition compositions typography colors : +48 506 780 943 : janwi@janwi.com

photo graphic Jan Witkowski Project for exhibition compositions typography colors : +48 506 780 943 : janwi@janwi.com Jan Witkowski : +48 506 780 943 : janwi@janwi.com Project for exhibition photo graphic compositions typography colors Berlin London Paris Barcelona Vienna Prague Krakow Zakopane Jan Witkowski ARTIST FROM

Bardziej szczegółowo

Analiza ryzyka jako instrument zarządzania środowiskiem

Analiza ryzyka jako instrument zarządzania środowiskiem WARSZTATY 2003 z cyklu Zagrożena naturalne w górnctwe Mat. Symp. str. 461 466 Elżbeta PILECKA, Małgorzata SZCZEPAŃSKA Instytut Gospodark Surowcam Mneralnym Energą PAN, Kraków Analza ryzyka jako nstrument

Bardziej szczegółowo

LOTNICZYM ZE SZCZEGÓLNYM

LOTNICZYM ZE SZCZEGÓLNYM PRACE NAUKOWE POLITECHNIKI WARSZAWSKIEJ z. 122 Transport 2018 Artur Kerzkowsk, Tomasz Ksel, Mara Pawlak edra Eksploatacj Systemów Logstycznych, Hydraulcznych LOTNICZYM ZE SZCZEGÓLNYM ODPRAWY BILETOWO-

Bardziej szczegółowo

ZASTOSOWANIE PROGRAMÓW PC-CRASH I V-SIM DO SYMULACJI RAJDOWEJ JAZDY SAMOCHODEM

ZASTOSOWANIE PROGRAMÓW PC-CRASH I V-SIM DO SYMULACJI RAJDOWEJ JAZDY SAMOCHODEM Potr Śwder Krzysztof Wach ZASTOSOWANIE PROGRAMÓW PC-CRASH I V-SIM DO SYMULACJI RAJDOWEJ JAZDY SAMOCHODEM Streszczene Podczas wypadku drogowego samochód bardzo często porusza sę ruchem odbegającym od ruchu

Bardziej szczegółowo

Machine Learning for Data Science (CS4786) Lecture 11. Spectral Embedding + Clustering

Machine Learning for Data Science (CS4786) Lecture 11. Spectral Embedding + Clustering Machine Learning for Data Science (CS4786) Lecture 11 Spectral Embedding + Clustering MOTIVATING EXAMPLE What can you say from this network? MOTIVATING EXAMPLE How about now? THOUGHT EXPERIMENT For each

Bardziej szczegółowo

PRZYPADKI KOMPLEKSOWEJ OCENY STANU TECHNICZNEGO IZOLACJI METODAMI PRĄDU STAŁEGO

PRZYPADKI KOMPLEKSOWEJ OCENY STANU TECHNICZNEGO IZOLACJI METODAMI PRĄDU STAŁEGO 1 Artur Polak BOBRME KOMEL, Katowce PRZYPADKI KOMPLEKSOWEJ OCENY STANU TECHNICZNEGO IZOLACJI METODAMI PRĄDU STAŁEGO CASES OF A COMPREHENSIVE EVALUATION OF INSULATION TECHNICAL CONDITION USING DC METHODS

Bardziej szczegółowo

Instrukcja konfiguracji usługi Wirtualnej Sieci Prywatnej w systemie Mac OSX

Instrukcja konfiguracji usługi Wirtualnej Sieci Prywatnej w systemie Mac OSX UNIWERSYTETU BIBLIOTEKA IEGO UNIWERSYTETU IEGO Instrukcja konfiguracji usługi Wirtualnej Sieci Prywatnej w systemie Mac OSX 1. Make a new connection Open the System Preferences by going to the Apple menu

Bardziej szczegółowo

Zadane 1: Wyznacz średne ruchome 3-okresowe z następujących danych obrazujących zużyce energ elektrycznej [kwh] w pewnym zakładze w mesącach styczeń - lpec 1998 r.: 400; 410; 430; 40; 400; 380; 370. Zadane

Bardziej szczegółowo

ANALIZA PORÓWNAWCZA WYNIKÓW UZYSKANYCH ZA POMOCĄ MIAR SYNTETYCZNYCH: M ORAZ PRZY ZASTOSOWANIU METODY UNITARYZACJI ZEROWANEJ

ANALIZA PORÓWNAWCZA WYNIKÓW UZYSKANYCH ZA POMOCĄ MIAR SYNTETYCZNYCH: M ORAZ PRZY ZASTOSOWANIU METODY UNITARYZACJI ZEROWANEJ METODY ILOŚCIOWE W BADANIACH EKONOMICZNYCH Tom XVI/3, 2015, str. 248 257 ANALIZA PORÓWNAWCZA WYNIKÓW UZYSKANYCH ZA POMOCĄ MIAR SYNTETYCZNYCH: M ORAZ PRZY ZASTOSOWANIU METODY UNITARYZACJI ZEROWANEJ Sławomr

Bardziej szczegółowo

WYKAZ PRÓB / SUMMARY OF TESTS. mgr ing. Janusz Bandel

WYKAZ PRÓB / SUMMARY OF TESTS. mgr ing. Janusz Bandel Sprawozdanie z Badań Nr Strona/Page 2/24 WYKAZ PRÓB / SUMMARY OF TESTS STRONA PAGE Próba uszkodzenia przy przepięciach dorywczych TOV failure test 5 Próby wykonał / The tests were carried out by: mgr ing.

Bardziej szczegółowo

Jak zasada Pareto może pomóc Ci w nauce języków obcych?

Jak zasada Pareto może pomóc Ci w nauce języków obcych? Jak zasada Pareto może pomóc Ci w nauce języków obcych? Artykuł pobrano ze strony eioba.pl Pokazuje, jak zastosowanie zasady Pareto może usprawnić Twoją naukę angielskiego. Słynna zasada Pareto mówi o

Bardziej szczegółowo

European Crime Prevention Award (ECPA) Annex I - new version 2014

European Crime Prevention Award (ECPA) Annex I - new version 2014 European Crime Prevention Award (ECPA) Annex I - new version 2014 Załącznik nr 1 General information (Informacje ogólne) 1. Please specify your country. (Kraj pochodzenia:) 2. Is this your country s ECPA

Bardziej szczegółowo

Planowanie eksperymentu pomiarowego I

Planowanie eksperymentu pomiarowego I POLITECHNIKA ŚLĄSKA W GLIWICACH WYDZIAŁ INŻYNIERII ŚRODOWISKA ENERGETYKI INSTYTUT MASZYN URZĄDZEŃ ENERGETYCZNYCH Plaowae eksperymetu pomarowego I Laboratorum merctwa (M 0) Opracował: dr ż. Grzegorz Wcak

Bardziej szczegółowo

Helena Boguta, klasa 8W, rok szkolny 2018/2019

Helena Boguta, klasa 8W, rok szkolny 2018/2019 Poniższy zbiór zadań został wykonany w ramach projektu Mazowiecki program stypendialny dla uczniów szczególnie uzdolnionych - najlepsza inwestycja w człowieka w roku szkolnym 2018/2019. Składają się na

Bardziej szczegółowo

SPITSBERGEN HORNSUND

SPITSBERGEN HORNSUND Polska Stacja Polarna Instytut Geofizyki Polska Akademia Nauk Polish Polar Station Institute of Geophysics Polish Academy of Sciences BIULETYN METEOROLOGICZNY METEOROLOGICAL BULLETIN SPITSBERGEN HORNSUND

Bardziej szczegółowo

The Diagrammatic Coaction

The Diagrammatic Coaction E H U N I V E R S I T T Y O H F R G E D I N B U The Dagrammatc Coacton Enan Gard (Hggs Centre, Ednburgh) In collaboraton wth: Samuel Abreu, Ruth Brtto, Claude Duhr and James Matthew References: Phys.Rev.Lett.

Bardziej szczegółowo

POMIAR WSPÓŁCZYNNIKÓW ODBICIA I PRZEPUSZCZANIA

POMIAR WSPÓŁCZYNNIKÓW ODBICIA I PRZEPUSZCZANIA Ćwczene O5 POMIAR WSPÓŁCZYNNIKÓW ODBICIA I PRZEPUSZCZANIA 1. Cel zakres ćwczena Celem ćwczena jest poznane metod pomaru współczynnków odbca przepuszczana próbek płaskch 2. Ops stanowska laboratoryjnego

Bardziej szczegółowo

Materiały z II Konferencji Naukowo-Technicznej "Diagnostyka w sieciach elektroenergetycznych zakładów przemysłowych", Płock, 2001, str.3-10.

Materiały z II Konferencji Naukowo-Technicznej Diagnostyka w sieciach elektroenergetycznych zakładów przemysłowych, Płock, 2001, str.3-10. Materały z II Konferencj Naukowo-Techncznej "Dagnostyka w secach elektroenergetycznych zakładów przemysłoch", Płock, 001, str.3-10. Andrzej OLENCKI Poltechnka Zelonogórska, 65-46 Zelona Góra, ul. Podgórna

Bardziej szczegółowo

1945 (96,1%) backlinks currently link back. 1505 (74,4%) links bear full SEO value. 0 links are set up using embedded object

1945 (96,1%) backlinks currently link back. 1505 (74,4%) links bear full SEO value. 0 links are set up using embedded object Website Backlinks Analysis Report 2023 backlinks from 224 domains Report created: Jan 3, 2015 Website: http://wpisz.stronę.odbiorcy Compared with: 7 day(s) old Domain Statistics The domain seo.zgred.pl

Bardziej szczegółowo

SPITSBERGEN HORNSUND

SPITSBERGEN HORNSUND Polska Stacja Polarna Instytut Geofizyki Polska Akademia Nauk Polish Polar Station Institute of Geophysics Polish Academy of Sciences BIULETYN METEOROLOGICZNY METEOROLOGICAL BULLETIN SPITSBERGEN HORNSUND

Bardziej szczegółowo

aforementioned device she also has to estimate the time when the patients need the infusion to be replaced and/or disconnected. Meanwhile, however, she must cope with many other tasks. If the department

Bardziej szczegółowo

Analysis of Movie Profitability STAT 469 IN CLASS ANALYSIS #2

Analysis of Movie Profitability STAT 469 IN CLASS ANALYSIS #2 Analysis of Movie Profitability STAT 469 IN CLASS ANALYSIS #2 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

Bardziej szczegółowo

Has the heat wave frequency or intensity changed in Poland since 1950?

Has the heat wave frequency or intensity changed in Poland since 1950? Has the heat wave frequency or intensity changed in Poland since 1950? Joanna Wibig Department of Meteorology and Climatology, University of Lodz, Poland OUTLINE: Motivation Data Heat wave frequency measures

Bardziej szczegółowo

6. ROŻNICE MIĘDZY OBSERWACJAMI STATYSTYCZNYMI RUCHU KOLEJOWEGO A SAMOCHODOWEGO

6. ROŻNICE MIĘDZY OBSERWACJAMI STATYSTYCZNYMI RUCHU KOLEJOWEGO A SAMOCHODOWEGO Różnce mędzy obserwacjam statystycznym ruchu kolejowego a samochodowego 7. ROŻNICE MIĘDZY OBSERWACJAMI STATYSTYCZNYMI RUCHU KOLEJOWEGO A SAMOCHODOWEGO.. Obserwacje odstępów mędzy kolejnym wjazdam na stację

Bardziej szczegółowo

Employment. Number of employees employed on a contract of employment by gender in 2012. Company

Employment. Number of employees employed on a contract of employment by gender in 2012. Company Im not found /sites/eneacsr2012.mess-asp.com/themes/eneacsr2012/img/enea.jpg Employt Capital Group is one of the largest companies in the energy industry. Therefore it has an influence, as an employer,

Bardziej szczegółowo

CEE 111/211 Agenda Feb 17

CEE 111/211 Agenda Feb 17 CEE 111/211 Agenda Feb 17 Tuesday: SW for project work: Jetstream, MSP, Revit, Riuska, POP, SV On R: drive; takes time to install Acoustics today: \\cife server\files\classes\cee111\presentations Thursday:

Bardziej szczegółowo

Pneumatyczne pomiary długości

Pneumatyczne pomiary długości Wrocław, dna Metrologa Welkośc Geometrycznych Ćwczene Rok kerunek... Grupa (dzeń godzna rozpoczęca zajęć) Pneumatyczne pomary długośc A. Wyznaczene charakterystyk statycznej czujnka pneumatycznego. Identyfkacja

Bardziej szczegółowo

SPITSBERGEN HORNSUND

SPITSBERGEN HORNSUND Polska Stacja Polarna Instytut Geofizyki Polska Akademia Nauk Polish Polar Station Institute of Geophysics Polish Academy of Sciences BIULETYN METEOROLOGICZNY METEOROLOGICAL BULLETIN SPITSBERGEN HORNSUND

Bardziej szczegółowo

Sargent Opens Sonairte Farmers' Market

Sargent Opens Sonairte Farmers' Market Sargent Opens Sonairte Farmers' Market 31 March, 2008 1V8VIZSV7EVKIRX8(1MRMWXIVSJ7XEXIEXXLI(ITEVXQIRXSJ%KVMGYPXYVI *MWLIVMIWERH*SSHTIVJSVQIHXLISJJMGMEPSTIRMRKSJXLI7SREMVXI*EVQIVW 1EVOIXMR0E]XS[R'S1IEXL

Bardziej szczegółowo

PROGNOZOWANIE SPRZEDAŻY Z ZASTOSOWANIEM ROZKŁADU GAMMA Z KOREKCJĄ ZE WZGLĘDU NA WAHANIA SEZONOWE

PROGNOZOWANIE SPRZEDAŻY Z ZASTOSOWANIEM ROZKŁADU GAMMA Z KOREKCJĄ ZE WZGLĘDU NA WAHANIA SEZONOWE STUDIA I PRACE WYDZIAŁU NAUK EKONOMICZNYCH I ZARZĄDZANIA NR 36 Krzysztof Dmytrów * Marusz Doszyń ** Unwersytet Szczecńsk PROGNOZOWANIE SPRZEDAŻY Z ZASTOSOWANIEM ROZKŁADU GAMMA Z KOREKCJĄ ZE WZGLĘDU NA

Bardziej szczegółowo

Automatyczne stanowisko pomiarowe do badań charakterystyk pracy plazmotronów łukowych

Automatyczne stanowisko pomiarowe do badań charakterystyk pracy plazmotronów łukowych Automatyczne stanowsko pomarowe do badań plazmotronów łukowych Jakub Szałatkewcz, Rafał Kłoda, Roman Szewczyk Przemysłowy Instytut Automatyk Pomarów PIAP, Warszawa Streszczene: W artykule przedstawono

Bardziej szczegółowo

XXX OLIMPIADA FIZYCZNA ETAP III Zadanie doświadczalne

XXX OLIMPIADA FIZYCZNA ETAP III Zadanie doświadczalne XXX OLIMPIADA FIZYCZNA ETAP III Zadane dośwadczalne ZADANIE D Nazwa zadana: Maszyna analogowa. Dane są:. doda półprzewodnkowa (krzemowa) 2. opornk dekadowy (- 5 Ω ), 3. woltomerz cyfrowy, 4. źródło napęca

Bardziej szczegółowo

Hybrydowe energetyczne filtry aktywne

Hybrydowe energetyczne filtry aktywne Ukazuje sę od 99 roku 7-8 07 Organ Stowarzyszena Elektryków Polskch Wydawnctwo SIGMA-NOT Sp. z o.o. Maran PASKO, Dawd BUŁA Poltechnka Śląska, Instytut Elektrotechnk Przemysłowej Informatyk Hybrydowe energetyczne

Bardziej szczegółowo

WYZNACZENIE CHARAKTERYSTYK DYNAMICZNYCH PRZETWORNIKÓW POMIAROWYCH

WYZNACZENIE CHARAKTERYSTYK DYNAMICZNYCH PRZETWORNIKÓW POMIAROWYCH Zakład Metrolog Systemów Pomarowych P o l t e c h n k a P o z n ańska ul. Jana Pawła II 6-965 POZNAŃ (budynek Centrum Mechatronk, Bomechank Nanonżyner) www.zmsp.mt.put.poznan.pl tel. +8 6 665 35 7 fa +8

Bardziej szczegółowo

Ankiety Nowe funkcje! Pomoc magda.szewczyk@slo-wroc.pl. magda.szewczyk@slo-wroc.pl. Twoje konto Wyloguj. BIODIVERSITY OF RIVERS: Survey to students

Ankiety Nowe funkcje! Pomoc magda.szewczyk@slo-wroc.pl. magda.szewczyk@slo-wroc.pl. Twoje konto Wyloguj. BIODIVERSITY OF RIVERS: Survey to students Ankiety Nowe funkcje! Pomoc magda.szewczyk@slo-wroc.pl Back Twoje konto Wyloguj magda.szewczyk@slo-wroc.pl BIODIVERSITY OF RIVERS: Survey to students Tworzenie ankiety Udostępnianie Analiza (55) Wyniki

Bardziej szczegółowo

Katowice, plan miasta: Skala 1: = City map = Stadtplan (Polish Edition)

Katowice, plan miasta: Skala 1: = City map = Stadtplan (Polish Edition) Katowice, plan miasta: Skala 1:20 000 = City map = Stadtplan (Polish Edition) Polskie Przedsiebiorstwo Wydawnictw Kartograficznych im. Eugeniusza Romera Click here if your download doesn"t start automatically

Bardziej szczegółowo

OPTYMALIZACJA WARTOŚCI POLA MAGNETYCZNEGO W POBLIŻU LINII NAPOWIETRZNEJ Z WYKORZYSTANIEM ALGORYTMU GENETYCZNEGO

OPTYMALIZACJA WARTOŚCI POLA MAGNETYCZNEGO W POBLIŻU LINII NAPOWIETRZNEJ Z WYKORZYSTANIEM ALGORYTMU GENETYCZNEGO POZNAN UNIVE RSITY OF TE CHNOLOGY ACADE MIC JOURNALS No 81 Electrcal Engneerng 015 Mkołaj KSIĄŻKIEWICZ* OPTYMALIZACJA WARTOŚCI POLA MAGNETYCZNEGO W POLIŻU LINII NAPOWIETRZNEJ Z WYKORZYSTANIEM ALGORYTMU

Bardziej szczegółowo