SENSITIVITY ANALYSIS OF POWER SYSTEM STABILITY FACTORS INCLUDING THE UNCERTAINTY OF MATHEMATICAL MODEL PARAMETERS

Wielkość: px
Rozpocząć pokaz od strony:

Download "SENSITIVITY ANALYSIS OF POWER SYSTEM STABILITY FACTORS INCLUDING THE UNCERTAINTY OF MATHEMATICAL MODEL PARAMETERS"

Transkrypt

1 ELEKTRYKA 2011 Zeszyt 2 (218) Rok LVII Adrian NOCOŃ, Stefan PASZEK Instytut Elektrotechniki i Informatyki, Politechnika Śląska w Gliwicach SENSITIVITY ANALYSIS OF POWER SYSTEM STABILITY FACTORS INCLUDING THE UNCERTAINTY OF MATHEMATICAL MODEL PARAMETERS Summary. The paper presents sensitivity analysis of the stability factors that can be used as criteria for further optimisation of power system stabilizers. The sensitivity of these factors to changes of selected mathematical model parameters of the sources connected to the medium voltage distribution network analysed was investigated. The obtained results were used for determining parameters of the models being more and less significant for the sensitivity analysis. The models taking into account nonlinearity were applied to modelling the system Keywords: power system, sensitivity, synchronous generator model, parameter uncertainty ANALIZA WRAŻLIWOŚCI WSKAŹNIKÓW STABILNOŚCI SYSTEMU Z UWZGLĘDNIENIEM NIEPEWNOŚCI PARAMETRÓW MODELI MATEMATYCZNYCH Streszczenie. W artykule przedstawiono analizę wrażliwości wskaźników stabilności mogących służyć jako kryteria do późniejszej optymalizacji stabilizatorów systemowych. Badano wrażliwość tychże wskaźników na wybrane parametry modeli matematycznych źródeł przyłączonych do analizowanej sieci dystrybucyjnej średniego napięcia. Uzyskane wyniki posłużyły do określenia parametrów modeli mniej i bardziej znaczących w analizie stabilności. Do modelowania systemu zastosowano modele z uwzględnieniem nieliniowości. Słowa kluczowe: wrażliwość, model generatora synchronicznego, model GENROU, niepewność parametrów 1. INTRODUCTION Stricter and stricter CO2 emission standards as well as the wish to diversify the electrical energy supply influence the dynamic development of renewable sources. These sources, usually of not large power, are more and more often installed in medium voltage distribution

2 8 A. Nocoń, S. Paszek networks. When there are appropriately many distributed sources in the network, there arise interactions between the working sources in transient states (caused by, for instance, shortcircuit or shut-down of one of the sources). These interactions can result in loss of the source stability and more serious failure consequences, including the power loss in the area covered by this network. Application of systems stabilizing the network operation, for instance appropriately selected excitation control systems or power system stabilizers (PPSs), can be a solution to this problem. Low power (up to 5 MW) distributed sources manufactured nowadays are most often equipped with standard control systems. On account of it, it would be uneconomical to equip them with system stabilizers without technical justification. Then, the stability analysis of operation of these sources, and in the case justified optimisation of control systems, including PSSs, becomes necessary. In order to optimise the PSSs, it is necessary to know the mathematical model of the system analysed and to determine disturbances that can be most threatening to the system (the distribution network in the case considered) stability [8]. The mathematical model, strictly speaking its parameters, is most often determined in the numerical estimation process, whereas the modal analysis is used for determining the disturbances that can be most threatening to the system stability [7]. In consequence, the quality of the PSS optimisation depends on the accuracy of representing transient states occurring in the network analysed. Due to not large powers of distributed sources, it would be difficult to find economical justification for complete investigations of the system in order to accurately determine all its parameters. On account of it, stability analyses have to be based on the mathematical model parameters estimated roughly. In consequence, it worsens the quality of the analysed PSS optimisation. Performing investigations based on the models whose significant parameters are accurately determined and the standard values assumed for the other parameters is a solution to this problem, which, in consequence, results in increase of the analysis accuracy. For such a solution it is necessary to determine more and less significant parameters. To do it, the sensitivity analysis can be used [5, 6]. There is presented an exemplary sensitivity analysis of the stability factors which can be used as criteria for further PSS optimisation. In this paper the waveforms of instantaneous power and angular speed deviation (that is quantities associated with electromechanical swings) as well as terminal voltage of particular generators for selected disturbances of the steady state are assumed to be the stability factors [7, 8]. There was investigated the sensitivity of these factors to selected mathematical model parameters of the sources connected to the medium voltage distribution network analysed. The obtained results were used for determining the models less and more significant for the stability analysis. For modelling the system there were used the models taking into account

3 Sensitivity analysis of power 9 the nonlinearity of magnetization characteristics. The package PSLF was used for simulation calculations [4]. 2. MATHEMATICAL MODEL OF POWER SYSTEM In the investigations presented the analysis was performed for the medium voltage distribution network being a part of the Polish power system (PPS). The network under consideration covers the area of about 100 km 2 inhabited, according to statistical data, by about 25 thousand of people. In this area there is one town of 14 km 2 area inhabited by 12 thousand people. The rest of this area contains rural grounds. The power network consists of 15 kv lines. Their total length is about 60 km. The lines supplying the town are cable lines of conductor diameters equal to 70 and 95 mm 2. The rural area is supplied mainly by overhead lines of conductor diameters equal to 35, 50 and 70 mm 2. PS L1 G2 G1 Fig. 1. Simplified diagram of the PS fragment analysed Rys. 1. Uproszczony schemat analizowanego fragmentu PS The analysed power system (PS) model consisted of 181 nodes, 191 lines, 85 loads (working at 0.4 kv voltage) and 5 generating units, in that one equivalent unit representing, in a simplified way, dynamics of the whole PPS. Additionally, there was modelled a 110 / 15 kv

4 10 A. Nocoń, S. Paszek transformer connecting the distribution network with the power system as well as 15 / 0.4 kv transformers supplying low voltage loads. The analysed system structure is shown in Fig. 1. Structure of generating units of the PS analysed Table 1 Generated power Type of mathematical models Generating unit representing the system equivalent 8.6 MW GENCLS Generating units of hydropower plants 2 x 1 MW GENSAL [1, 9] EXST1 [2, 9], HYGOV [3, 9] Generating units of wind power plants 3 x 1 MW GENWRI, EXWTG1, WNDTRB [4] It was assumed that there are two small 1 MW hydropower plants located at the town outskirts (G1 and G2 in Fig. 1) working at nominal power. Moreover, there were taken into account in the system three 1.65 MW wind power plants built in the rural area. These plants are equipped with asynchronous generators controlled by resistance change in the rotor circuit. It was assumed that the wind power plants work at the power equal to 0.6 nominal power, that is each of them produces about 1 MW power. The analysed system structure and the models assumed for analysis are presented in Table 1. For simulation investigations the line was modelled with an impedance model of type which takes into account the resistance and longitudinal reactance of the line and its capacity. The network parameters (line resistances and reactances) were assumed according to the data of its operator. 3. SENSITIVITY ANALYSIS OF PS STABILITY FACTORS In the investigations presented there was determined the sensitivity of three quantities associated with the system stability and describing the transient state of the generating unit G1. The waveforms were determined for the transient state caused by three-phase passing short-circuit in the line L1 (the short-circuit place is marked in Fig. 1) as well as for the transient state caused by sudden shut-down of all wind farms generation. The waveforms of the instantaneous power deviation p(t), the terminal voltage deviation u(t) as well as the rotation speed change (t) were investigated under these transient conditions. It was assumed that these waveforms were connected with the PS stability factors. The halfrelative sensitivity was used for estimation of the selected waveform sensitivity to the parameter changes. Due to the fact that the sensitivity values depend on time, the sensitivity was assumed to have integral form:

5 Sensitivity analysis of power 11 S S q1 q2 t q( t) x t x t 0 t x i 0 xi i q( t) i dt, (1) 2 dt, (2) where: q(t) the waveform for which the sensitivity is determined ( p(t), u(t) or (t)), xi the parameter in relation to which the sensitivity is determined, t time of the transient state analysis. The sensitivity analysis of the waveforms was performed for the following parameters of the models: transient time constant in d axis of generator G1 - Td0G1', transient reactance in d axis of generator G1 - XdG1', inertia time constant of generating unit G1 - HG1, transient time constant in d axis of generator G2 - Td0G2', transient reactance in d axis of generator G2 - XdG2', inertia time constant of generating unit G2 - HG2, inertia time constant of generating unit representing the PPS equivalent - HPS. In order to take into account the uncertainty of parameters in relation to which the sensitivity was determined, the parameter xi value was replaced with the probability distribution of the given parameter k(xi) value occurrence. There was assumed in calculations that all probabilities are of normal distribution for which the average value is x i and the range is ±25%. In the investigations presented the probability distribution of the parameters was determined based on the analysis of the catalogue data of mass-produced generators. There were analysed 72 generators of rated powers from 50 kv A to 1000 kv A produced by two manufacturers. The detailed analysis is contained in [6]. The exemplary probability distribution for the transient time constants in d axis of generators G1 and G2 - Td0' is shown in Fig. 2. The average values for the other parameters of ' generators G1 and G2 are: X d = 0,205 p.u., H = 5,23 s, whereas for the unit representing the PPS equivalent H PS = 3 s. Fig. 2. Probability distribution for the transient time constant in d axis of generator G1 Rys. 2. Rozkład prawdopodobieństwa dla przejściowej stałej czasowej w osi d generatora G1 Simulation investigations leading to determining the sensitivity when taking into account the uncertainty of the mathematical model parameters consist in performing repeated calculations for randomly chosen parameter values according to the assumed probability

6 12 A. Nocoń, S. Paszek distribution (Fig. 2). In this case the calculation results are bands of the selected waveforms (instantaneous powers, terminal voltage and rotational speed of the unit G1) and, in consequence, bands of the sensitivity waveforms. All bands obtained are characterised by the limit values (for instance, the maximum and minimum values) and the average value. In the investigations presented the average values were determined for 100 sets of parameters chosen randomly according to the assumed probability. The bands of the waveforms of the instantaneous power, terminal voltage and rotational speed of the generating unit G1 for short-circuit in the line L1 are shown in Fig. 3a, while for shut-down of wind power plants generation in Fig. 3b. Figs. 4-7 present the waveforms of the sensitivity factors (1) and (2) for short-circuit and shut-down of wind power plants generation, respectively. In order to make the figures legible, there are shown only the average values of the sensitivity factors. a) b) Fig. 3. Bands of the waveforms of instantaneous power p(t), terminal voltage u(t) and rotational speed (t) of generator G1 for short-circuit in line L1 (a) and shut-down of wind power plants generation (b) Rys. 3. Pasma przebiegów mocy chwilowej p(t), napięcia zaciskowego u(t) i prędkości wirowania (t) generatora G1 przy zwarciu w linii L1 (a) i wyłączeniu generacji siłowni wiatrowych (b)

7 Sensitivity analysis of power 13 Fig. 4. Waveforms of the average value of the sensitivity factors S p(t), S u(t), S (t) of generator G1 for short-circuit in line L1 (sensitivity factors (1)) Rys. 4. Przebiegi średniej wartości wskaźników wrażliwości S p(t), S u(t), S (t) generatora G1 przy zwarciu w linii L1 (wg zależności (1)) Fig. 5. Waveforms of the average value of the sensitivity factors S p(t), S u(t), S (t) of generator G1 for short-circuit in line L1 (sensitivity factors (2)) Rys. 5. Przebiegi średniej wartości wskaźników wrażliwości S p(t), S u(t), S (t) generatora G1 przy zwarciu w linii L1 (wg zależności (2)) Fig. 6. Waveforms of the average value of the sensitivity factors S p(t), S u(t), S (t) of generator G1 for shut-down of wind power plants generation (sensitivity factors (1)) Rys. 6. Przebiegi średniej wartości wskaźników wrażliwości S p(t), S u(t), S (t) generatora G1 przy wyłączeniu generacji siłowni wiatrowych (wg zależności (1))

8 14 A. Nocoń, S. Paszek Fig. 7. Waveforms of the average value of the sensitivity factors S p(t), S u(t), S (t) of generator G1 for shut-down of wind power plants generation (sensitivity factors (2)) Rys. 7. Przebiegi średniej wartości wskaźników wrażliwości S p(t), S u(t), S (t) generatora G1 przy wyłączeniu generacji siłowni wiatrowych (wg zależności (2)) 4. SUMMARY The following conclusions can be drawn from the calculations performed: - The sensitivity factors (1-2) for particular generator output quantities and model parameters have different waveforms for different disturbances. However, it can be noted that the greatest and least instantaneous values of particular factors are most often connected with the same parameters. The parameters connected with great values of the appropriate factors are relatively well (with a small error) calculated in the estimation process. When estimating the parameters of particular models, it is possible to use different objective functions analogical to the sensitivity factors defined. Hence, it is recommended to use for estimation an objective function taking into account many waveforms. - The waveforms of the instantaneous power and rotational speed of generators for the disturbances analysed are especially sensitive to changes of the inertia time constant of particular generators. The generator terminal voltage waveforms are highly sensitive to the changes of the synchronous reactance Xd and transient time constant Td0' of generators. Due to it, these quantities should be determined particularly accurately in the parameter estimation process of the PS element mathematical models. If necessary, the estimation inaccuracy of these parameters should be taken into consideration when optimising and polyoptimising the parameters of PPSs working in the PS of uncertain parameters. - Based on the sensitivity analysis of the generator output quantities to the change of the model parameters, it can be noted that it is possible to choose such an objective function (for instance multiplicative or additive) that its sensitivity to particular parameters should be increased.

9 Sensitivity analysis of power 15 - The transient state duration has significant influence on the sensitivity value, and as a consequence, on the objective function value assumed for generator parameter estimation. BIBLIOGRAPHY 1. De Mello, F. P., Hannett, L. H.: Representation of Saturation in Synchronous Machines IEEE Transactions on Power Systems. 1986, Vol. PWRS-1, No. 4, p Excitation System Subcommittee IEEE Computer Models for Representation of Digital- Based Excitation Systems. 3. IEEE Committee Report, Dynamic Models for Steam and Hydro Turbines in Power System Studies, IEEE Transactions on Power Apparatus and Systems 1973, Vol. PAS- 92, No. 6, p Miller N. W., Price W. W., Sanchez - Gasca J. J.: Stability modeling of Vestas V80 wind turbine generator. GE PSLF, March Nocoń A., Pasko M., Paszek S.: Sensitivity analysis including uncertainty of synchronous generator model parameters. 9th International Conference Control of Power Systems 10, Tatranské Matliare, Slovak Republic, June 2010, p Nocoń A., Szuster D.: Distributed source mathematical model including parameter uncertainty. 33th International Conference on Fundamentals of Electrotechnics and Circuit Theory, SPETO 2010, Ustroń-May 2009, p Paszek S.: Optimisation of PSS parameters. Journal of Electrical Engineering. Slovak Centrum of IEE. 2001, Vol. 52, p Paszek S., Pawłowski A.: Parameter optimization of dual input power system stabilizers PSS3B in multi-machine power system. International Conference of Fundamentals of Electrotechnics and Circuit Theory 2004, Vol. 2, p Power Technologies, a Division of S&W Consultants Inc., Program PSS/E Application Guide. This work was partly financed by the Polish Ministry of Science and Higher Education from means of budget on science in years as research project N N Wpłynęło do Redakcji dnia 16 maja 2011 r. Recenzent: Prof. dr hab. inż. Marian Łukaniszyn

10 16 A. Nocoń, S. Paszek Omówienie Przy optymalizacji parametrów stabilizatorów systemowych konieczna jest znajomość modelu matematycznego analizowanego systemu elektroenergetycznego, w skład którego może wchodzić m in. sieć dystrybucyjna średniego napięcia. Ze względu na niewielkie moce źródeł pracujących w sieci dystrybucyjnej, trudno byłoby znaleźć ekonomiczne uzasadnienie pełnych badań systemu w celu dokładnego wyznaczenia wszystkich jego parametrów. W związku z tym analizy stabilności muszą być oparte na zgrubnie oszacowanych parametrach modeli matematycznych. Rozwiązaniem tego problemu, a w konsekwencji zwiększenie dokładności analizy, może być przeprowadzenie badań na podstawie modeli, w których dokładnie wyznaczono parametry znaczące, wpływające w znacznym stopniu na analizowane wskaźniki stabilności, natomiast dla pozostałych przyjęto wartości standardowe. W celu określenia parametrów, mniej lub bardziej wpływających na wybrane wskaźniki, można zastosować analizę wrażliwości. W niniejszym artykule przedstawiono przykładową analizę wrażliwości wskaźników stabilności, mogących służyć jako kryteria przy optymalizacji parametrów stabilizatorów systemowych. Jako wskaźniki stabilności przyjęto przebiegi mocy chwilowej i odchyłki prędkości kątowej oraz napięcia zaciskowego poszczególnych generatorów przy wybranych zakłóceniach stanu ustalonego. Badano wrażliwość tych wskaźników na wybrane parametry modeli matematycznych źródeł przyłączonych do analizowanej sieci dystrybucyjnej średniego napięcia. Uzyskane wyniki posłużyły do określenia parametrów modeli mniej i bardziej znaczących w analizie stabilności. W prezentowanych badaniach analizę przeprowadzono dla sieci dystrybucyjnej średniego napięcia, stanowiącej fragment polskiego systemu elektroenergetycznego. Rozpatrywana sieć obejmowała obszar około 100 km 2. Sieć elektroenergetyczną stanowią linie o napięciu 15 kv o długości ok. 60 km. Model analizowanego systemu składał się ze 181 węzłów w tym 5 węzłów wytwórczych. Strukturę analizowanego systemu przedstawiono na rys. 1. Założono, że w rozpatrywanym systemie pracują dwie małe elektrownie wodne (G1 i G2 na rys. 1) o mocy 1 MW. Ponadto, w systemie uwzględniono trzy siłownie wiatrowe o mocy 1,65 MW. W prezentowanych badaniach wyznaczano wrażliwość wybranych przebiegów w stanach przejściowych wywołanych przez trójfazowe przemijające zwarcie w linii L1 oraz nagłym wyłączeniem generacji wszystkich farm wiatrowych. Do oceny wpływu zmian parametrów na wybrane przebiegi wykorzystano wrażliwość półwzględną zgodnie z zależnościami (1) i (2). Przy czym analizę wrażliwości przebiegów przeprowadzono dla wybranych parametrów modeli generatora G1, generatora G2 i zespołu wytwórczego reprezentującego zastępczy ekwiwalent pozostałej reszty systemu. Uwzględnienie niepewności parametrów, względem których wyznaczano wrażliwość, nastąpiło poprzez zastąpienie konkretnej wartości parametru rozkładem prawdopodobieństwa

11 Sensitivity analysis of power 17 wystąpienia danej wartości parametru. W obliczeniach założono, że wszystkie prawdopodobieństwa mają rozkład normalny (rys. 2). Badania symulacyjne prowadzące do wyznaczenia wrażliwości z uwzględnieniem niepewności parametrów modelu matematycznego polegają na wielokrotnym powtarzaniu obliczeń przy losowo wybieranych wartościach parametrów, zgodnie z założonym rozkładem prawdopodobieństwa. Wynikami obliczeń są w tym przypadku pasma przebiegów wybranych wielkości, a w konsekwencji pasma przebiegów wrażliwości. W przedstawionych badaniach wartości średnie określono dla 100 zestawów parametrów wylosowanych zgodnie z przyjętym prawdopodobieństwem. Pasma przebiegów mocy chwilowej, napięcia zaciskowego i prędkości kątowej generatora dla zespołu wytwórczego G1 przedstawiono na rys. 3. Na rys. od 4 do 7 przedstawiono przebiegi wskaźników wrażliwości (1) i (2), odpowiednio dla zwarcia i wyłączenia generacji siłowni wiatrowych. Przy czym ze względu na czytelność rysunku na wykresach tych przedstawiono tylko wartości średnie wskaźników wrażliwości. Z przeprowadzonych obliczeń wyciągnięto następujące wnioski ogólne: - Wyznaczone wskaźniki wrażliwości dla poszczególnych parametrów modelu generatora mają różne przebiegi dla różnych zakłóceń. Jednak można zauważyć, że największe i najmniejsze wartości chwilowe poszczególnych wskaźników są najczęściej związane z tymi samymi parametrami, które są stosunkowo dobrze (z małym błędem) obliczane w procesie estymacji. Dlatego też zaleca się stosowanie, przy estymacji parametrów odpowiednich modeli, funkcji celu, uwzględniającej wiele przebiegów zakłóceniowych. - Przebiegi mocy chwilowej i prędkości kątowej generatorów przy analizowanych zakłóceniach są szczególnie wrażliwe na zmianę wartości stałej czasowej inercji poszczególnych generatorów. Przebiegi napięcia zaciskowego generatorów są wrażliwe w dużym stopniu na zmiany reaktancji synchronicznej i stałej czasowej podprzejściowej generatorów. W związku z tym te wielkości powinny być szczególnie dokładnie określone w procesie estymacji parametrów modeli matematycznych. Ewentualne niedokładności estymacji tych parametrów trzeba uwzględniać przy optymalizacji i polioptymalizacji parametrów stabilizatorów systemowych, pracujących w systemie elektroenergetycznym o niepewnych parametrach.

BADANIA SYMULACYJNE STANÓW PRZEJŚCIOWYCH GENERATORÓW ŹRÓDEŁ ROZPROSZONYCH

BADANIA SYMULACYJNE STANÓW PRZEJŚCIOWYCH GENERATORÓW ŹRÓDEŁ ROZPROSZONYCH Prace Naukowe Instytutu Maszyn, Napędów i Pomiarów Elektrycznych Nr 66 Politechniki Wrocławskiej Nr 66 Studia i Materiały Nr 32 2012 Adrian NOCOŃ*, Dominik SZUSTER* generatory, źródła rozproszone, badania

Bardziej szczegółowo

STABILIZATION OF VIRTUAL POWER PLANT SOURCES STABILIZACJA ŹRÓDEŁ W ELEKTROWNI WIRTUALNEJ ELEKTRYKA 2009

STABILIZATION OF VIRTUAL POWER PLANT SOURCES STABILIZACJA ŹRÓDEŁ W ELEKTROWNI WIRTUALNEJ ELEKTRYKA 2009 ELEKTRYKA 009 Zeszyt (0) Rok LV Stefan PASZEK, Adrian NOCOŃ Instytut Elektrotechniki i Informatyki, Politechnika Śląska w Gliwicach STABILIZATION OF VIRTUAL POWER PLANT SOURCES Summary. The paper presents

Bardziej szczegółowo

ELEKTROMECHANICZNE STANY PRZEJŚCIOWE ŹRÓDEŁ ROZPROSZONYCH PRACUJĄCYCH W SIECI DYSTRYBUCYJNEJ

ELEKTROMECHANICZNE STANY PRZEJŚCIOWE ŹRÓDEŁ ROZPROSZONYCH PRACUJĄCYCH W SIECI DYSTRYBUCYJNEJ ELEKRYKA 2015 Zeszyt 4 (236) Rok LXI Dominik SZUSER Adrian NOCOŃ Stefan PASZEK Instytut Elektrotechniki i Informatyki Politechnika Śląska w Gliwicach ELEKROMECHANICZNE SANY PRZEJŚCIOWE ŹRÓDEŁ ROZPROSZONYCH

Bardziej szczegółowo

DUAL SIMILARITY OF VOLTAGE TO CURRENT AND CURRENT TO VOLTAGE TRANSFER FUNCTION OF HYBRID ACTIVE TWO- PORTS WITH CONVERSION

DUAL SIMILARITY OF VOLTAGE TO CURRENT AND CURRENT TO VOLTAGE TRANSFER FUNCTION OF HYBRID ACTIVE TWO- PORTS WITH CONVERSION ELEKTRYKA 0 Zeszyt (9) Rok LX Andrzej KUKIEŁKA Politechnika Śląska w Gliwicach DUAL SIMILARITY OF VOLTAGE TO CURRENT AND CURRENT TO VOLTAGE TRANSFER FUNCTION OF HYBRID ACTIVE TWO- PORTS WITH CONVERSION

Bardziej szczegółowo

PORÓWNANIE STANÓW PRZEJŚCIOWYCH MIKROŹRÓDEŁ Z GENERATOREM ASYNCHRONICZNYM I SYNCHRONICZNYM

PORÓWNANIE STANÓW PRZEJŚCIOWYCH MIKROŹRÓDEŁ Z GENERATOREM ASYNCHRONICZNYM I SYNCHRONICZNYM Zeszyty Problemowe Maszyny Elektryczne Nr 3/2014 (103) 193 Adrian Nocoń, Dominik Szuster, Stefan Paszek Politechnik Śląska, Instytut Elektrotechniki i Informatyki PORÓWNANIE STANÓW PRZEJŚCIOWYCH MIKROŹRÓDEŁ

Bardziej szczegółowo

SYNCHRONOUS GENERATOR FIELD-CIRCUIT MODEL AND ITS VERIFICATION BY MEASUREMENTS

SYNCHRONOUS GENERATOR FIELD-CIRCUIT MODEL AND ITS VERIFICATION BY MEASUREMENTS ELEKTRYKA 2009 Zeszyt 2 (210) Rok LV Sebastian BERHAUSEN, Andrzej BOBOŃ, Stefan PASZEK Instytut Elektrotechniki i Informatyki, Politechnika Śląska w Gliwicach SYNCHRONOUS GENERATOR FIELD-CIRCUIT MODEL

Bardziej szczegółowo

Rozpoznawanie twarzy metodą PCA Michał Bereta 1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów

Rozpoznawanie twarzy metodą PCA Michał Bereta   1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów Rozpoznawanie twarzy metodą PCA Michał Bereta www.michalbereta.pl 1. Testowanie statystycznej istotności różnic między jakością klasyfikatorów Wiemy, że możemy porównywad klasyfikatory np. za pomocą kroswalidacji.

Bardziej szczegółowo

Machine Learning for Data Science (CS4786) Lecture 11. Spectral Embedding + Clustering

Machine Learning for Data Science (CS4786) Lecture 11. Spectral Embedding + Clustering Machine Learning for Data Science (CS4786) Lecture 11 Spectral Embedding + Clustering MOTIVATING EXAMPLE What can you say from this network? MOTIVATING EXAMPLE How about now? THOUGHT EXPERIMENT For each

Bardziej szczegółowo

Proposal of thesis topic for mgr in. (MSE) programme in Telecommunications and Computer Science

Proposal of thesis topic for mgr in. (MSE) programme in Telecommunications and Computer Science Proposal of thesis topic for mgr in (MSE) programme 1 Topic: Monte Carlo Method used for a prognosis of a selected technological process 2 Supervisor: Dr in Małgorzata Langer 3 Auxiliary supervisor: 4

Bardziej szczegółowo

Towards Stability Analysis of Data Transport Mechanisms: a Fluid Model and an Application

Towards Stability Analysis of Data Transport Mechanisms: a Fluid Model and an Application Towards Stability Analysis of Data Transport Mechanisms: a Fluid Model and an Application Gayane Vardoyan *, C. V. Hollot, Don Towsley* * College of Information and Computer Sciences, Department of Electrical

Bardziej szczegółowo

REHABILITATION OF MEDIUM-HEAD HYDROPOWER PLANTS WITH EXPLOITED TWIN-FRANCIS TURBINES.

REHABILITATION OF MEDIUM-HEAD HYDROPOWER PLANTS WITH EXPLOITED TWIN-FRANCIS TURBINES. ZRE Gdańsk S.A. ul. Litewska 14A 80-719 Gdańsk REHABILITATION OF MEDIUM-HEAD HYDROPOWER PLANTS WITH EXPLOITED TWIN-FRANCIS TURBINES. Maciej Kaniecki, PhD Andrzej Łojek, PhD Marusz Hajdarowicz, M.Sc.Eng

Bardziej szczegółowo

ELEKTRYKA 2013 Zeszyt 2-3 ( )

ELEKTRYKA 2013 Zeszyt 2-3 ( ) ELEKTRYKA 2013 Zeszyt 2-3 (226-227) Rok LIX Adrian NOCOŃ, Dominik SZUSTER Politechnika Śląska w Gliwicach ZASTOSOWANIE ALGORYTMU GENETYCZNEGO DO OCENY JAKOŚCI REGULACJI MIKROŹRÓDŁA ENERGII EKLEKTRYCZNEJ

Bardziej szczegółowo

NATĘŻENIE POLA ELEKTRYCZNEGO PRZEWODU LINII NAPOWIETRZNEJ Z UWZGLĘDNIENIEM ZWISU

NATĘŻENIE POLA ELEKTRYCZNEGO PRZEWODU LINII NAPOWIETRZNEJ Z UWZGLĘDNIENIEM ZWISU POZNAN UNIVE RSITY OF TE CHNOLOGY ACADE MIC JOURNALS No 85 Electrical Engineering 016 Krzysztof KRÓL* NATĘŻENIE POLA ELEKTRYCZNEGO PRZEWODU LINII NAPOWIETRZNEJ Z UWZGLĘDNIENIEM ZWISU W artykule zaprezentowano

Bardziej szczegółowo

ELECTRIC AND MAGNETIC FIELDS NEAR NEW POWER TRANSMISSION LINES POLA ELEKTRYCZNE I MAGNETYCZNE WOKÓŁ NOWYCH LINII ELEKTROENERGETYCZNYCH

ELECTRIC AND MAGNETIC FIELDS NEAR NEW POWER TRANSMISSION LINES POLA ELEKTRYCZNE I MAGNETYCZNE WOKÓŁ NOWYCH LINII ELEKTROENERGETYCZNYCH ELEKTRYKA 2012 Zeszyt 3-4 (223-224) Rok LVIII Olgierd MAŁYSZKO, Michał ZEŃCZAK Katedra Elektroenergetyki i Napędów Elektrycznych, Zachodniopomorski Uniwersytet Technologiczny w Szczecinie w Szczecinie

Bardziej szczegółowo

Zakopane, plan miasta: Skala ok. 1: = City map (Polish Edition)

Zakopane, plan miasta: Skala ok. 1: = City map (Polish Edition) Zakopane, plan miasta: Skala ok. 1:15 000 = City map (Polish Edition) Click here if your download doesn"t start automatically Zakopane, plan miasta: Skala ok. 1:15 000 = City map (Polish Edition) Zakopane,

Bardziej szczegółowo

OCENA STABILNOŚCI KĄTOWEJ KRAJOWEGO SYSTEMU ELEKTROENERGETYCZNEGO NA PODSTAWIE ANALIZY PRZEBIEGÓW ZAKŁÓCENIOWYCH MOCY CHWILOWEJ

OCENA STABILNOŚCI KĄTOWEJ KRAJOWEGO SYSTEMU ELEKTROENERGETYCZNEGO NA PODSTAWIE ANALIZY PRZEBIEGÓW ZAKŁÓCENIOWYCH MOCY CHWILOWEJ Prace Naukowe Instytutu Maszyn, Napędów i Pomiarów Elektrycznych Nr 66 Politechniki Wrocławskiej Nr 66 Studia i Materiały Nr 32 2012 Piotr PRUSKI, Stefan PASZEK* system elektroenergetyczny, wartości własne

Bardziej szczegółowo

Akademia Morska w Szczecinie. Wydział Mechaniczny

Akademia Morska w Szczecinie. Wydział Mechaniczny Akademia Morska w Szczecinie Wydział Mechaniczny ROZPRAWA DOKTORSKA mgr inż. Marcin Kołodziejski Analiza metody obsługiwania zarządzanego niezawodnością pędników azymutalnych platformy pływającej Promotor:

Bardziej szczegółowo

EXAMPLES OF CABRI GEOMETRE II APPLICATION IN GEOMETRIC SCIENTIFIC RESEARCH

EXAMPLES OF CABRI GEOMETRE II APPLICATION IN GEOMETRIC SCIENTIFIC RESEARCH Anna BŁACH Centre of Geometry and Engineering Graphics Silesian University of Technology in Gliwice EXAMPLES OF CABRI GEOMETRE II APPLICATION IN GEOMETRIC SCIENTIFIC RESEARCH Introduction Computer techniques

Bardziej szczegółowo

POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH

POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH POLITECHNIKA ŚLĄSKA INSTYTUT AUTOMATYKI ZAKŁAD SYSTEMÓW POMIAROWYCH Gliwice, wrzesień 2005 Pomiar napięcia przemiennego Cel ćwiczenia Celem ćwiczenia jest zbadanie dokładności woltomierza cyfrowego dla

Bardziej szczegółowo

ESTYMACJA PARAMETRÓW PRZEMYSŁOWEGO ZESPOŁU WYTWÓRCZEGO O MOCY 7.5 MVA NA PODSTAWIE TESTU ZANIKU PRĄDU STAŁEGO

ESTYMACJA PARAMETRÓW PRZEMYSŁOWEGO ZESPOŁU WYTWÓRCZEGO O MOCY 7.5 MVA NA PODSTAWIE TESTU ZANIKU PRĄDU STAŁEGO ELEKTRYKA 013 Zeszyt 4 (8) Rok LIX Łukasz MAJKA, Dominik SZUSTER Politechnika Śląska w Gliwicach ESTYMACJA PARAMETRÓW PRZEMYSŁOWEGO ZESPOŁU WYTWÓRCZEGO O MOCY 7.5 MVA NA PODSTAWIE TESTU ZANIKU PRĄDU STAŁEGO

Bardziej szczegółowo

ZJAWISKA W OBWODACH TŁUMIĄCYCH PODCZAS ZAKŁÓCEŃ PRACY TURBOGENERATORA

ZJAWISKA W OBWODACH TŁUMIĄCYCH PODCZAS ZAKŁÓCEŃ PRACY TURBOGENERATORA Prace Naukowe Instytutu Maszyn, Napędów i Pomiarów Elektrycznych Nr 66 Politechniki Wrocławskiej Nr 66 Studia i Materiały Nr 32 212 Piotr KISIELEWSKI*, Ludwik ANTAL* maszyny synchroniczne, turbogeneratory,

Bardziej szczegółowo

Fig 5 Spectrograms of the original signal (top) extracted shaft-related GAD components (middle) and

Fig 5 Spectrograms of the original signal (top) extracted shaft-related GAD components (middle) and Fig 4 Measured vibration signal (top). Blue original signal. Red component related to periodic excitation of resonances and noise. Green component related. Rotational speed profile used for experiment

Bardziej szczegółowo

RADIO DISTURBANCE Zakłócenia radioelektryczne

RADIO DISTURBANCE Zakłócenia radioelektryczne AKREDYTOWANE LABORATORIUM BADAWCZE Page (Strona) 2 of (Stron) 9 Following requirements should be taken into account in the case of making use of Test Report and giving information about the tests performed

Bardziej szczegółowo

www.irs.gov/form990. If "Yes," complete Schedule A Schedule B, Schedule of Contributors If "Yes," complete Schedule C, Part I If "Yes," complete Schedule C, Part II If "Yes," complete Schedule C, Part

Bardziej szczegółowo

Wykaz linii kolejowych, które są wyposażone w urządzenia systemu ETCS

Wykaz linii kolejowych, które są wyposażone w urządzenia systemu ETCS Wykaz kolejowych, które są wyposażone w urządzenia W tablicy znajdującej się na kolejnych stronach tego załącznika zastosowano następujące oznaczenia: - numer kolejowej według instrukcji Wykaz Id-12 (D-29).

Bardziej szczegółowo

Krytyczne czynniki sukcesu w zarządzaniu projektami

Krytyczne czynniki sukcesu w zarządzaniu projektami Seweryn SPAŁEK Krytyczne czynniki sukcesu w zarządzaniu projektami MONOGRAFIA Wydawnictwo Politechniki Śląskiej Gliwice 2004 SPIS TREŚCI WPROWADZENIE 5 1. ZARZĄDZANIE PROJEKTAMI W ORGANIZACJI 13 1.1. Zarządzanie

Bardziej szczegółowo

PORTS AS LOGISTICS CENTERS FOR CONSTRUCTION AND OPERATION OF THE OFFSHORE WIND FARMS - CASE OF SASSNITZ

PORTS AS LOGISTICS CENTERS FOR CONSTRUCTION AND OPERATION OF THE OFFSHORE WIND FARMS - CASE OF SASSNITZ Part-financed by EU South Baltic Programme w w w. p t m e w. p l PROSPECTS OF THE OFFSHORE WIND ENERGY DEVELOPMENT IN POLAND - OFFSHORE WIND INDUSTRY IN THE COASTAL CITIES AND PORT AREAS PORTS AS LOGISTICS

Bardziej szczegółowo

Helena Boguta, klasa 8W, rok szkolny 2018/2019

Helena Boguta, klasa 8W, rok szkolny 2018/2019 Poniższy zbiór zadań został wykonany w ramach projektu Mazowiecki program stypendialny dla uczniów szczególnie uzdolnionych - najlepsza inwestycja w człowieka w roku szkolnym 2018/2019. Składają się na

Bardziej szczegółowo

Wykaz linii kolejowych, które są wyposażone w urzadzenia systemu ETCS

Wykaz linii kolejowych, które są wyposażone w urzadzenia systemu ETCS Wykaz kolejowych, które są wyposażone w urzadzenia W tablicy znajdującej się na kolejnych stronach tego załącznika zastosowano następujące oznaczenia: - numer kolejowej według instrukcji Wykaz Id-12 (D-29).

Bardziej szczegółowo

USE OF HYBRID OPTIMISATION ALGORITHM FOR ELECTROMAGNETIC PARAMETER ESTIMATION OF A SYNCHRONOUS GENERATOR

USE OF HYBRID OPTIMISATION ALGORITHM FOR ELECTROMAGNETIC PARAMETER ESTIMATION OF A SYNCHRONOUS GENERATOR ELEKTRYKA 2009 Zeszyt 2 (210) Rok LV Łukasz MAJKA, Stefan PASZEK Instytut Elektrotechniki i Informatyki, Politechnika Śląska w Gliwicach USE OF HYBRID OPTIMISATION ALGORITHM FOR ELECTROMAGNETIC PARAMETER

Bardziej szczegółowo

PARAMETRY TECHNICZNE DEKLAROWANE PRZEZ PRODUCENTA POTWIERDZONE BADANIAMI / RATINGS ASSIGNED BY THE MANUFACTURER AND PROVED BY TESTS

PARAMETRY TECHNICZNE DEKLAROWANE PRZEZ PRODUCENTA POTWIERDZONE BADANIAMI / RATINGS ASSIGNED BY THE MANUFACTURER AND PROVED BY TESTS Sprawozdanie z Strona/Page 2/24 PARAMETRY TECHNICZNE DEKLAROWANE PRZEZ PRODUCENTA POTWIERDZONE BADANIAMI / RATINGS ASSIGNED BY THE MANUFACTURER AND PROVED BY TESTS Typ Type Napięcie trwałej pracy Continuous

Bardziej szczegółowo

Patients price acceptance SELECTED FINDINGS

Patients price acceptance SELECTED FINDINGS Patients price acceptance SELECTED FINDINGS October 2015 Summary With growing economy and Poles benefiting from this growth, perception of prices changes - this is also true for pharmaceuticals It may

Bardziej szczegółowo

TTIC 31210: Advanced Natural Language Processing. Kevin Gimpel Spring Lecture 9: Inference in Structured Prediction

TTIC 31210: Advanced Natural Language Processing. Kevin Gimpel Spring Lecture 9: Inference in Structured Prediction TTIC 31210: Advanced Natural Language Processing Kevin Gimpel Spring 2019 Lecture 9: Inference in Structured Prediction 1 intro (1 lecture) Roadmap deep learning for NLP (5 lectures) structured prediction

Bardziej szczegółowo

RADIO DISTURBANCE Zakłócenia radioelektryczne

RADIO DISTURBANCE Zakłócenia radioelektryczne AKREDYTOWANE LABORATORIUM BADAWCZE Page (Strona) 2 of (Stron) 9 Following requirements should be taken into account in the case of making use of Test Report and giving information about the tests performed

Bardziej szczegółowo

www.irs.gov/form990. If "Yes," complete Schedule A Schedule B, Schedule of Contributors If "Yes," complete Schedule C, Part I If "Yes," complete Schedule C, Part II If "Yes," complete Schedule C, Part

Bardziej szczegółowo

WARUNKI ZWARCIOWE W ROZDZIELNI SPOWODOWANE ZAKŁÓCENIAMI NA RÓŻNYCH ELEMENTACH SIECI ELEKTROENERGETYCZNEJ

WARUNKI ZWARCIOWE W ROZDZIELNI SPOWODOWANE ZAKŁÓCENIAMI NA RÓŻNYCH ELEMENTACH SIECI ELEKTROENERGETYCZNEJ POZNAN UNIVE RSITY OF TE CHNOLOGY ACADE MIC JOURNALS No 86 Electrical Engineering 2016 Piotr PIECHOCKI* Ryszard FRĄCKOWIAK** WARUNKI ZWARCIOWE W ROZDZIELNI SPOWODOWANE ZAKŁÓCENIAMI NA RÓŻNYCH ELEMENTACH

Bardziej szczegółowo

WYKAZ PRÓB / SUMMARY OF TESTS. mgr ing. Janusz Bandel

WYKAZ PRÓB / SUMMARY OF TESTS. mgr ing. Janusz Bandel Sprawozdanie z Badań Nr Strona/Page 2/24 WYKAZ PRÓB / SUMMARY OF TESTS STRONA PAGE Próba uszkodzenia przy przepięciach dorywczych TOV failure test 5 Próby wykonał / The tests were carried out by: mgr ing.

Bardziej szczegółowo

Machine Learning for Data Science (CS4786) Lecture11. Random Projections & Canonical Correlation Analysis

Machine Learning for Data Science (CS4786) Lecture11. Random Projections & Canonical Correlation Analysis Machine Learning for Data Science (CS4786) Lecture11 5 Random Projections & Canonical Correlation Analysis The Tall, THE FAT AND THE UGLY n X d The Tall, THE FAT AND THE UGLY d X > n X d n = n d d The

Bardziej szczegółowo

Few-fermion thermometry

Few-fermion thermometry Few-fermion thermometry Phys. Rev. A 97, 063619 (2018) Tomasz Sowiński Institute of Physics of the Polish Academy of Sciences Co-authors: Marcin Płodzień Rafał Demkowicz-Dobrzański FEW-BODY PROBLEMS FewBody.ifpan.edu.pl

Bardziej szczegółowo

Analiza porównawcza zmian w rozbiorach wody z uwzględnieniem sposobu jej dostarczania do odbiorców

Analiza porównawcza zmian w rozbiorach wody z uwzględnieniem sposobu jej dostarczania do odbiorców 55 Analiza porównawcza zmian w rozbiorach wody z uwzględnieniem sposobu jej dostarczania do odbiorców Politechnika Koszalińska 1. Wstęp W związku z zaobserwowanym systematycznym zmniejszaniem się zużycia

Bardziej szczegółowo

ZASTOSOWANIE SPLOTU FUNKCJI DO OPISU WŁASNOŚCI NIEZAWODNOŚCIOWYCH UKŁADÓW Z REZERWOWANIEM

ZASTOSOWANIE SPLOTU FUNKCJI DO OPISU WŁASNOŚCI NIEZAWODNOŚCIOWYCH UKŁADÓW Z REZERWOWANIEM 1-2011 PROBLEMY EKSPLOATACJI 205 Zbigniew ZDZIENNICKI, Andrzej MACIEJCZYK Politechnika Łódzka, Łódź ZASTOSOWANIE SPLOTU FUNKCJI DO OPISU WŁASNOŚCI NIEZAWODNOŚCIOWYCH UKŁADÓW Z REZERWOWANIEM Słowa kluczowe

Bardziej szczegółowo

Estimation of Selected Synchronous Generator Parameters Based on the Gradient Method

Estimation of Selected Synchronous Generator Parameters Based on the Gradient Method Estimation of Selected Synchronous Generator Parameters Based on the Gradient Method Authors Zbigniew Lubośny Jacek Klucznik Krzysztof Dobrzyński Keywords synchronous generator model, estimation, gradient

Bardziej szczegółowo

THE DEVELOPMENT OF THE REAL LIFE MODEL OF THE FIVE NODE POWER SYSTEM STRUKTURA I ANALIZA PRACY PIĘCIOWĘZŁOWEGO SYSTEMU ELEKTROENERGETYCZNEGO

THE DEVELOPMENT OF THE REAL LIFE MODEL OF THE FIVE NODE POWER SYSTEM STRUKTURA I ANALIZA PRACY PIĘCIOWĘZŁOWEGO SYSTEMU ELEKTROENERGETYCZNEGO TECHNICAL TRANSACTIONS ELECTRICAL ENGINEERING CZASOPISMO TECHNICZNE ELEKTROTECHNIKA 2-E/2015 JERZY SZCZEPANIK*, BARTOSZ ROZEGNAŁ* THE DEVELOPMENT OF THE REAL LIFE MODEL OF THE FIVE NODE POWER SYSTEM STRUKTURA

Bardziej szczegółowo

WARTOŚCI CZASU TRWANIA ZWARCIA PODCZAS ZAKŁÓCEŃ W ROZDZIELNIACH NAJWYŻSZYCH NAPIĘĆ W ŚWIETLE BADAŃ SYMULACYJNYCH

WARTOŚCI CZASU TRWANIA ZWARCIA PODCZAS ZAKŁÓCEŃ W ROZDZIELNIACH NAJWYŻSZYCH NAPIĘĆ W ŚWIETLE BADAŃ SYMULACYJNYCH POZNAN UNIVE RSITY OF TE CHNOLOGY ACADE MIC JOURNALS No 78 Electrical Engineering 2014 Ryszard FRĄCKOWIAK* Piotr PIECHOCKI** WARTOŚCI CZASU TRWANIA ZWARCIA PODCZAS ZAKŁÓCEŃ W ROZDZIELNIACH NAJWYŻSZYCH

Bardziej szczegółowo

Hard-Margin Support Vector Machines

Hard-Margin Support Vector Machines Hard-Margin Support Vector Machines aaacaxicbzdlssnafiyn9vbjlepk3ay2gicupasvu4iblxuaw2hjmuwn7ddjjmxm1bkcg1/fjqsvt76fo9/gazqfvn8y+pjpozw5vx8zkpvtfxmlhcwl5zxyqrm2vrg5zw3vxmsoezi4ogkr6phieky5crvvjhriqvdom9l2xxftevuwcekj3lktmhghgniauiyutvrwxtvme34a77kbvg73gtygpjsrfati1+xc8c84bvraowbf+uwnipyehcvmkjrdx46vlykhkgykm3ujjdhcyzqkxy0chur6ax5cbg+1m4bbjptjcubuz4kuhvjoql93hkin5hxtav5x6yyqopnsyuneey5ni4keqrxbar5wqaxbik00icyo/iveiyqqvjo1u4fgzj/8f9x67bzmxnurjzmijtlybwfgcdjgfdtajwgcf2dwaj7ac3g1ho1n4814n7wwjgjmf/ys8fenfycuzq==

Bardziej szczegółowo

Tematyka prac doktorskich 1. Bezczujnikowe sterowanie oraz estymacja parametrów maszyn wielofazowych zasilanych przekształtnikowo

Tematyka prac doktorskich 1. Bezczujnikowe sterowanie oraz estymacja parametrów maszyn wielofazowych zasilanych przekształtnikowo Dr hab. inż. Marcin Morawiec Katedra Automatyki Napędu Elektrycznego Wydział Elektrotechniki i Automatyki Politechnika Gdańska Budynek EM, ul. Sobieskiego 7, pok. 218, tel. 58 347 11 76 Dyscyplina: elektrotechnika

Bardziej szczegółowo

Przewody elektroenergetyczne z izolacją XLPE

Przewody elektroenergetyczne z izolacją XLPE Przewody elektroenergetyczne z izolacją XLPE Power cables with XLPE insulation AsXSn 0,6/1 kv Norma Standard PN HD 626 4F 2 1 Konstrukcja Construction Żyła przewodząca aluminiowa Aluminium 1 2 Izolacja

Bardziej szczegółowo

XXIII Konferencja Naukowa POJAZDY SZYNOWE 2018

XXIII Konferencja Naukowa POJAZDY SZYNOWE 2018 XXIII Konferencja Naukowa POJAZDY SZYNOWE 2018 Abstract Application of longitudinal dynamics of the train in the simulator of catenary maintenance vehicles - experimental and numerical tests Robert Konowrocki

Bardziej szczegółowo

TYRE PYROLYSIS. REDUXCO GENERAL DISTRIBUTOR :: ::

TYRE PYROLYSIS. REDUXCO GENERAL DISTRIBUTOR  ::   :: TYRE PYROLYSIS Installation for rubber waste pyrolysis designed for processing of used tyres and plastic waste (polyethylene, polypropylene, polystyrene), where the final product could be electricity,

Bardziej szczegółowo

Weronika Mysliwiec, klasa 8W, rok szkolny 2018/2019

Weronika Mysliwiec, klasa 8W, rok szkolny 2018/2019 Poniższy zbiór zadań został wykonany w ramach projektu Mazowiecki program stypendialny dla uczniów szczególnie uzdolnionych - najlepsza inwestycja w człowieka w roku szkolnym 2018/2019. Tresci zadań rozwiązanych

Bardziej szczegółowo

Knovel Math: Jakość produktu

Knovel Math: Jakość produktu Knovel Math: Jakość produktu Knovel jest agregatorem materiałów pełnotekstowych dostępnych w formacie PDF i interaktywnym. Narzędzia interaktywne Knovel nie są stworzone wokół specjalnych algorytmów wymagających

Bardziej szczegółowo

NIEPEWNOŚĆ POMIARÓW POZIOMU MOCY AKUSTYCZNEJ WEDŁUG ZNOWELIZOWANEJ SERII NORM PN-EN ISO 3740

NIEPEWNOŚĆ POMIARÓW POZIOMU MOCY AKUSTYCZNEJ WEDŁUG ZNOWELIZOWANEJ SERII NORM PN-EN ISO 3740 PRACE INSTYTUTU TECHNIKI BUDOWLANEJ - KWARTALNIK BUILDING RESEARCH INSTITUTE - QUARTERLY 2 (162) 2012 ARTYKUŁY - REPORTS Anna Iżewska* NIEPEWNOŚĆ POMIARÓW POZIOMU MOCY AKUSTYCZNEJ WEDŁUG ZNOWELIZOWANEJ

Bardziej szczegółowo

Sargent Opens Sonairte Farmers' Market

Sargent Opens Sonairte Farmers' Market Sargent Opens Sonairte Farmers' Market 31 March, 2008 1V8VIZSV7EVKIRX8(1MRMWXIVSJ7XEXIEXXLI(ITEVXQIRXSJ%KVMGYPXYVI *MWLIVMIWERH*SSHTIVJSVQIHXLISJJMGMEPSTIRMRKSJXLI7SREMVXI*EVQIVW 1EVOIXMR0E]XS[R'S1IEXL

Bardziej szczegółowo

MS Visual Studio 2005 Team Suite - Performance Tool

MS Visual Studio 2005 Team Suite - Performance Tool MS Visual Studio 2005 Team Suite - Performance Tool przygotował: Krzysztof Jurczuk Politechnika Białostocka Wydział Informatyki Katedra Oprogramowania ul. Wiejska 45A 15-351 Białystok Streszczenie: Dokument

Bardziej szczegółowo

Wprowadzenie do programu RapidMiner, część 2 Michał Bereta 1. Wykorzystanie wykresu ROC do porównania modeli klasyfikatorów

Wprowadzenie do programu RapidMiner, część 2 Michał Bereta  1. Wykorzystanie wykresu ROC do porównania modeli klasyfikatorów Wprowadzenie do programu RapidMiner, część 2 Michał Bereta www.michalbereta.pl 1. Wykorzystanie wykresu ROC do porównania modeli klasyfikatorów Zaimportuj dane pima-indians-diabetes.csv. (Baza danych poświęcona

Bardziej szczegółowo

Latent Dirichlet Allocation Models and their Evaluation IT for Practice 2016

Latent Dirichlet Allocation Models and their Evaluation IT for Practice 2016 Latent Dirichlet Allocation Models and their Evaluation IT for Practice 2016 Paweł Lula Cracow University of Economics, Poland pawel.lula@uek.krakow.pl Latent Dirichlet Allocation (LDA) Documents Latent

Bardziej szczegółowo

aforementioned device she also has to estimate the time when the patients need the infusion to be replaced and/or disconnected. Meanwhile, however, she must cope with many other tasks. If the department

Bardziej szczegółowo

SILNIK RELUKTANCYJNY PRZEŁĄCZALNY PRZEZNACZONY DO NAPĘDU MAŁEGO MOBILNEGO POJAZDU ELEKTRYCZNEGO

SILNIK RELUKTANCYJNY PRZEŁĄCZALNY PRZEZNACZONY DO NAPĘDU MAŁEGO MOBILNEGO POJAZDU ELEKTRYCZNEGO Prace Naukowe Instytutu Maszyn, Napędów i Pomiarów Elektrycznych Nr 66 Politechniki Wrocławskiej Nr 66 Studia i Materiały Nr 32 2012 Piotr BOGUSZ*, Mariusz KORKOSZ*, Jan PROKOP* silnik reluktancyjny przełączalny,

Bardziej szczegółowo

Linear Classification and Logistic Regression. Pascal Fua IC-CVLab

Linear Classification and Logistic Regression. Pascal Fua IC-CVLab Linear Classification and Logistic Regression Pascal Fua IC-CVLab 1 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

Bardziej szczegółowo

COMPARED ANALYSIS OF LSPMSM AND SQUIRREL-CAGE MOTOR EXPLOITATION WITH VARIABLE ROTATIONAL SPEED

COMPARED ANALYSIS OF LSPMSM AND SQUIRREL-CAGE MOTOR EXPLOITATION WITH VARIABLE ROTATIONAL SPEED TECHNICAL TRANSACTIONS ELECTRICAL ENGINEERING CZASOPISMO TECHNICZNE ELEKTROTECHNIKA 1-E/2015 PAWEŁ Idziak, Mariusz Barański, Wiesław Łyskawiński * COMPARED ANALYSIS OF LSPMSM AND SQUIRREL-CAGE MOTOR EXPLOITATION

Bardziej szczegółowo

Selection of controller parameters Strojenie regulatorów

Selection of controller parameters Strojenie regulatorów Division of Metrology and Power Processes Automation Selection of controller parameters Strojenie regulatorów A-9 Automatics laboratory Laboratorium automatyki Developed by//opracował: mgr inż. Wojciech

Bardziej szczegółowo

MULTI CRITERIA EVALUATION OF WIRELESS LOCAL AREA NETWORK DESIGNS

MULTI CRITERIA EVALUATION OF WIRELESS LOCAL AREA NETWORK DESIGNS STUDIA INFORMATICA 2015 Volume 36 Number 2 (120) Remigiusz OLEJNIK West Pomeranian University of Technology, Szczecin, Faculty of Computer Science and Information Technology MULTI CRITERIA EVALUATION OF

Bardziej szczegółowo

Tychy, plan miasta: Skala 1: (Polish Edition)

Tychy, plan miasta: Skala 1: (Polish Edition) Tychy, plan miasta: Skala 1:20 000 (Polish Edition) Poland) Przedsiebiorstwo Geodezyjno-Kartograficzne (Katowice Click here if your download doesn"t start automatically Tychy, plan miasta: Skala 1:20 000

Bardziej szczegółowo

Instrukcja obsługi User s manual

Instrukcja obsługi User s manual Instrukcja obsługi User s manual Konfigurator Lanberg Lanberg Configurator E-mail: support@lanberg.pl support@lanberg.eu www.lanberg.pl www.lanberg.eu Lanberg 2015-2018 WERSJA VERSION: 2018/11 Instrukcja

Bardziej szczegółowo

SPIS TREŚCI SPIS WAŻNIEJSZYCH OZNACZEŃ WSTĘP KRÓTKA CHARAKTERYSTYKA SEKTORA ENERGETYCZNEGO W POLSCE... 14

SPIS TREŚCI SPIS WAŻNIEJSZYCH OZNACZEŃ WSTĘP KRÓTKA CHARAKTERYSTYKA SEKTORA ENERGETYCZNEGO W POLSCE... 14 SPIS TREŚCI SPIS WAŻNIEJSZYCH OZNACZEŃ... 9 1. WSTĘP... 11 2. KRÓTKA CHARAKTERYSTYKA SEKTORA ENERGETYCZNEGO W POLSCE... 14 2.1. Analiza aktualnego stanu struktury wytwarzania elektryczności i ciepła w

Bardziej szczegółowo

RESONANCE OF TORSIONAL VIBRATION OF SHAFTS COUPLED BY MECHANISMS

RESONANCE OF TORSIONAL VIBRATION OF SHAFTS COUPLED BY MECHANISMS SCIENTIFIC BULLETIN OF LOZ TECHNICAL UNIVERSITY Nr 78, TEXTILES 55, 997 ZESZYTY NAUKOWE POLITECHNIKI ŁÓZKIEJ Nr 78, WŁÓKIENNICTWO z. 55, 997 Pages: 8- http://bhp-k4.p.loz.pl/ JERZY ZAJACZKOWSKI Loz Technical

Bardziej szczegółowo

STEROWANIA RUCHEM KOLEJOWYM Z WYKORZYSTANIEM METOD SYMULACYJNYCH

STEROWANIA RUCHEM KOLEJOWYM Z WYKORZYSTANIEM METOD SYMULACYJNYCH PRACE NAUKOWE POLITECHNIKI WARSZAWSKIEJ z. 113 Transport 2016 Uniwersytet Technologiczno-Humanistyczny w Radomiu STEROWANIA RUCHEM KOLEJOWYM Z WYKORZYSTANIEM METOD SYMULACYJNYCH : marzec 2016 Streszczenie:

Bardziej szczegółowo

ARNOLD. EDUKACJA KULTURYSTY (POLSKA WERSJA JEZYKOWA) BY DOUGLAS KENT HALL

ARNOLD. EDUKACJA KULTURYSTY (POLSKA WERSJA JEZYKOWA) BY DOUGLAS KENT HALL Read Online and Download Ebook ARNOLD. EDUKACJA KULTURYSTY (POLSKA WERSJA JEZYKOWA) BY DOUGLAS KENT HALL DOWNLOAD EBOOK : ARNOLD. EDUKACJA KULTURYSTY (POLSKA WERSJA Click link bellow and free register

Bardziej szczegółowo

PRACE NAUKOWE POLITECHNIKI WARSZAWSKIEJ

PRACE NAUKOWE POLITECHNIKI WARSZAWSKIEJ PRACE NAUKOWE POLITECHNIKI WARSZAWSKIEJ z. 111 Transport 16 : marzec 16 Streszczenie: - 1, 6, 1, 11, 1, 7 z innymi systemami [1 1, 1,, 7 przewidzianym charakterze. 17 1, 11, 1, 1,, 7, 1 POWROTNA refie

Bardziej szczegółowo

Cracow University of Economics Poland. Overview. Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005

Cracow University of Economics Poland. Overview. Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005 Cracow University of Economics Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005 - Key Note Speech - Presented by: Dr. David Clowes The Growth Research Unit CE Europe

Bardziej szczegółowo

Zarządzanie sieciami telekomunikacyjnymi

Zarządzanie sieciami telekomunikacyjnymi SNMP Protocol The Simple Network Management Protocol (SNMP) is an application layer protocol that facilitates the exchange of management information between network devices. It is part of the Transmission

Bardziej szczegółowo

IDENTYFIKACJA PARAMETRÓW CHARAKTERYZUJĄCYCH OBCIĄŻENIE SEKCJI OBUDOWY ZMECHANIZOWANEJ SPOWODOWANE DYNAMICZNYM ODDZIAŁYWANIEM GÓROTWORU

IDENTYFIKACJA PARAMETRÓW CHARAKTERYZUJĄCYCH OBCIĄŻENIE SEKCJI OBUDOWY ZMECHANIZOWANEJ SPOWODOWANE DYNAMICZNYM ODDZIAŁYWANIEM GÓROTWORU POLITECHNIKA ŚLĄSKA ZESZYTY NAUKOWE Nr 1648 Stanisław SZWEDA STJB Gottingen 217 808 00X IDENTYFIKACJA PARAMETRÓW CHARAKTERYZUJĄCYCH OBCIĄŻENIE SEKCJI OBUDOWY ZMECHANIZOWANEJ SPOWODOWANE DYNAMICZNYM ODDZIAŁYWANIEM

Bardziej szczegółowo

Energetyczna ocena efektywności pracy elektrociepłowni gazowo-parowej z organicznym układem binarnym

Energetyczna ocena efektywności pracy elektrociepłowni gazowo-parowej z organicznym układem binarnym tom XLI(2011), nr 1, 59 64 Władysław Nowak AleksandraBorsukiewicz-Gozdur Roksana Mazurek Zachodniopomorski Uniwersytet Technologiczny Wydział Inżynierii Mechanicznej i Mechatroniki Katedra Techniki Cieplnej

Bardziej szczegółowo

Rev Źródło:

Rev Źródło: KAmduino UNO Rev. 20190119182847 Źródło: http://wiki.kamamilabs.com/index.php/kamduino_uno Spis treści Basic features and parameters... 1 Standard equipment... 2 Electrical schematics... 3 AVR ATmega328P

Bardziej szczegółowo

Cracow University of Economics Poland

Cracow University of Economics Poland Cracow University of Economics Poland Sources of Real GDP per Capita Growth: Polish Regional-Macroeconomic Dimensions 2000-2005 - Keynote Speech - Presented by: Dr. David Clowes The Growth Research Unit,

Bardziej szczegółowo

POLITECHNIKA WARSZAWSKA. Wydział Zarządzania ROZPRAWA DOKTORSKA. mgr Marcin Chrząścik

POLITECHNIKA WARSZAWSKA. Wydział Zarządzania ROZPRAWA DOKTORSKA. mgr Marcin Chrząścik POLITECHNIKA WARSZAWSKA Wydział Zarządzania ROZPRAWA DOKTORSKA mgr Marcin Chrząścik Model strategii promocji w zarządzaniu wizerunkiem regionu Warmii i Mazur Promotor dr hab. Jarosław S. Kardas, prof.

Bardziej szczegółowo

Statystyczna analiza zmienności obciążeń w sieciach rozdzielczych Statistical Analysis of the Load Variability in Distribution Network

Statystyczna analiza zmienności obciążeń w sieciach rozdzielczych Statistical Analysis of the Load Variability in Distribution Network Statystyczna analiza zmienności obciążeń w sieciach rozdzielczych Statistical Analysis of the Load Variability in Distribution Network Wojciech Zalewski Politechnika Białostocka, Wydział Zarządzania, Katedra

Bardziej szczegółowo

Extraclass. Football Men. Season 2009/10 - Autumn round

Extraclass. Football Men. Season 2009/10 - Autumn round Extraclass Football Men Season 2009/10 - Autumn round Invitation Dear All, On the date of 29th July starts the new season of Polish Extraclass. There will be live coverage form all the matches on Canal+

Bardziej szczegółowo

Nazwa projektu: Kreatywni i innowacyjni uczniowie konkurencyjni na rynku pracy

Nazwa projektu: Kreatywni i innowacyjni uczniowie konkurencyjni na rynku pracy Nazwa projektu: Kreatywni i innowacyjni uczniowie konkurencyjni na rynku pracy DZIAŁANIE 3.2 EDUKACJA OGÓLNA PODDZIAŁANIE 3.2.1 JAKOŚĆ EDUKACJI OGÓLNEJ Projekt współfinansowany przez Unię Europejską w

Bardziej szczegółowo

OPTYMALIZACJA PUBLICZNEGO TRANSPORTU ZBIOROWEGO W GMINIE ŚRODA WIELKOPOLSKA

OPTYMALIZACJA PUBLICZNEGO TRANSPORTU ZBIOROWEGO W GMINIE ŚRODA WIELKOPOLSKA Politechnika Poznańska Wydział Maszyn Roboczych i Transportu Inż. NATALIA LEMTIS OPTYMALIZACJA PUBLICZNEGO TRANSPORTU ZBIOROWEGO W GMINIE ŚRODA WIELKOPOLSKA Promotor: DR INŻ. MARCIN KICIŃSKI Poznań, 2016

Bardziej szczegółowo

QUANTITATIVE AND QUALITATIVE CHARACTERISTICS OF FINGERPRINT BIOMETRIC TEMPLATES

QUANTITATIVE AND QUALITATIVE CHARACTERISTICS OF FINGERPRINT BIOMETRIC TEMPLATES ZESZYTY NAUKOWE POLITECHNIKI ŚLĄSKIEJ 2014 Seria: ORGANIZACJA I ZARZĄDZANIE z. 74 Nr kol. 1921 Adrian KAPCZYŃSKI Politechnika Śląska Instytut Ekonomii i Informatyki QUANTITATIVE AND QUALITATIVE CHARACTERISTICS

Bardziej szczegółowo

ESTYMACJA PARAMETRÓW DYNAMICZNYCH GENERATORÓW SYNCHRONICZNYCH

ESTYMACJA PARAMETRÓW DYNAMICZNYCH GENERATORÓW SYNCHRONICZNYCH ELEKTRYKA 2015 Zeszyt 1 (233) Rok LI Stefan PASZEK, Sebastian BERHAUSEN, Andrzej BOBOŃ, Łukasz MAJKA, Adrian NOCOŃ, Marian PASKO, Piotr PRUSKI, Tomasz KRASZEWSKI, Dominik SZUSTER Politechnika Śląska w

Bardziej szczegółowo

Przeciwpożarowe sterowniki dla bram zwijanych, sekcyjnych i przesuwnych. Fire-proof controls for roller shutters, sectional doors and sliding gates

Przeciwpożarowe sterowniki dla bram zwijanych, sekcyjnych i przesuwnych. Fire-proof controls for roller shutters, sectional doors and sliding gates Przeciwpożarowe napędy bram Charakterystyka Characteristics Fire-proof door drives 36 Przeciwpożarowe sterowniki dla bram zwijanych, sekcyjnych i przesuwnych Fire-proof controls for roller shutters, sectional

Bardziej szczegółowo

ELEKTRYKA Marcin NIEDOPYTALSKI Instytut Elektroenergetyki i Sterowania Układów, Politechnika Śląska w Gliwicach

ELEKTRYKA Marcin NIEDOPYTALSKI Instytut Elektroenergetyki i Sterowania Układów, Politechnika Śląska w Gliwicach ELEKTRYKA Zeszyt 2 (234) Rok LXI Marcin NIEDOPYTALSKI Instytut Elektroenergetyki i Sterowania Układów, Politechnika Śląska w Gliwicach OCENA ZDOLNOŚCI WYKRYWANIA ZWARĆ POŚREDNICH DLA RÓŻNYCH SPOSOBÓW PARAMETRYZACJI

Bardziej szczegółowo

Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards

Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards INSPIRE Conference 2010 INSPIRE as a Framework for Cooperation Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards Elżbieta Bielecka Agnieszka Zwirowicz

Bardziej szczegółowo

P R A C A D Y P L O M O W A

P R A C A D Y P L O M O W A POLITECHNIKA POZNAŃSKA Wydział Maszyn Roboczych i Transportu P R A C A D Y P L O M O W A Autor: inż. METODA Ε-CONSTRAINTS I PRZEGLĄDU FRONTU PARETO W ZASTOSOWANIU DO ROZWIĄZYWANIA PROBLEMU OPTYMALIZACJI

Bardziej szczegółowo

Katowice, plan miasta: Skala 1: = City map = Stadtplan (Polish Edition)

Katowice, plan miasta: Skala 1: = City map = Stadtplan (Polish Edition) Katowice, plan miasta: Skala 1:20 000 = City map = Stadtplan (Polish Edition) Polskie Przedsiebiorstwo Wydawnictw Kartograficznych im. Eugeniusza Romera Click here if your download doesn"t start automatically

Bardziej szczegółowo

OPTYMALIZACJA STEROWANIA MIKROKLIMATEM W PIECZARKARNI

OPTYMALIZACJA STEROWANIA MIKROKLIMATEM W PIECZARKARNI Inżynieria Rolnicza 6(131)/2011 OPTYMALIZACJA STEROWANIA MIKROKLIMATEM W PIECZARKARNI Leonard Woroncow, Ewa Wachowicz Katedra Automatyki, Politechnika Koszalińska Streszczenie. W pracy przedstawiono wyniki

Bardziej szczegółowo

KOMPUTEROWE MODELOWANIE SIECI WODOCIĄGOWYCH JAKO NARZĘDZIE DO ANALIZY PRĘDKOŚCI PRZEPŁYWU WODY

KOMPUTEROWE MODELOWANIE SIECI WODOCIĄGOWYCH JAKO NARZĘDZIE DO ANALIZY PRĘDKOŚCI PRZEPŁYWU WODY Wojciech KRUSZYŃSKI * systemy zaopatrzenia w wodę, komputerowe modelowanie sieci wodociągowych, wodociągi, modelowanie KOMPUTEROWE MODELOWANIE SIECI WODOCIĄGOWYCH JAKO NARZĘDZIE DO ANALIZY PRĘDKOŚCI PRZEPŁYWU

Bardziej szczegółowo

BLACKLIGHT SPOT 400W F

BLACKLIGHT SPOT 400W F BLACKLIGHT SPOT 400W F2000339 USER MANUAL / INSTRUKCJA OBSŁUGI BLACKLIGHT SPOT 400W F2000339 Table of Contents 1 Introduction... 2 2 Safety information... 2 3 Product information... 2 3.1 Specification...

Bardziej szczegółowo

www.irs.gov/form990. If "Yes," complete Schedule A Schedule B, Schedule of Contributors If "Yes," complete Schedule C, Part I If "Yes," complete Schedule C, Part II If "Yes," complete Schedule C, Part

Bardziej szczegółowo

WSPÓŁCZYNNIK MOCY I SPRAWNOŚĆ INDUKCYJNYCH SILNIKÓW JEDNOFAZOWYCH W WARUNKACH PRACY OPTYMALNEJ

WSPÓŁCZYNNIK MOCY I SPRAWNOŚĆ INDUKCYJNYCH SILNIKÓW JEDNOFAZOWYCH W WARUNKACH PRACY OPTYMALNEJ Maszyny Elektryczne Zeszyty Problemowe Nr 3/2015 (107) 167 Henryk Banach Politechnika Lubelska, Lublin WSPÓŁCZYNNIK MOCY I SPRAWNOŚĆ INDUKCYJNYCH SILNIKÓW JEDNOFAZOWYCH W WARUNKACH PRACY OPTYMALNEJ POWER

Bardziej szczegółowo

Installation of EuroCert software for qualified electronic signature

Installation of EuroCert software for qualified electronic signature Installation of EuroCert software for qualified electronic signature for Microsoft Windows systems Warsaw 28.08.2019 Content 1. Downloading and running the software for the e-signature... 3 a) Installer

Bardziej szczegółowo

Power cables with XLPE insulation

Power cables with XLPE insulation Przewody elektroenergetyczne z izolacją XLPE Power cables with XLPE insulation Norma PN HD 626 4F Standard 2 1 Konstrukcja: Construction: 1. Żyła przewodząca aluminiowa Aluminium 2. Izolacja XLPE XLPE

Bardziej szczegółowo

DM-ML, DM-FL. Auxiliary Equipment and Accessories. Damper Drives. Dimensions. Descritpion

DM-ML, DM-FL. Auxiliary Equipment and Accessories. Damper Drives. Dimensions. Descritpion DM-ML, DM-FL Descritpion DM-ML and DM-FL actuators are designed for driving round dampers and square multi-blade dampers. Example identification Product code: DM-FL-5-2 voltage Dimensions DM-ML-6 DM-ML-8

Bardziej szczegółowo

TRANSPORT W RODZINNYCH GOSPODARSTWACH ROLNYCH

TRANSPORT W RODZINNYCH GOSPODARSTWACH ROLNYCH INŻYNIERIA W ROLNICTWIE. MONOGRAFIE 16 ENGINEERING IN AGRICULTURE. MONOGRAPHS 16 WIESŁAW GOLKA TRANSPORT W RODZINNYCH GOSPODARSTWACH ROLNYCH TRANSPORTATION IN RURAL FAMILY FARMS Falenty 2014 WYDAWNICTWO

Bardziej szczegółowo

WYBRANE PROBLEMY BADAWCZE EKOLOGII, ORGANIZACJI I INFRASTRUKTURY TRANSPORTU

WYBRANE PROBLEMY BADAWCZE EKOLOGII, ORGANIZACJI I INFRASTRUKTURY TRANSPORTU POLITECHNIKA WARSZAWSKA ISSN 1230 9265 PRACE NAUKOWE TRANSPORT z. 106 WYBRANE PROBLEMY BADAWCZE EKOLOGII, ORGANIZACJI I INFRASTRUKTURY TRANSPORTU OFICYNA WYDAWNICZA POLITECHNIKI WARSZAWSKIEJ WARSZAWA 2015

Bardziej szczegółowo

HYBRID ACTIVE POWER FILTER UNDER DISTORTED MAINS VOLTAGE CONDITIONS HYBRYDOWY ENERGETYCZNY FILTR AKTYWNY W WARUNKACH ODKSZTAŁCONEGO NAPIĘCIA SIECI

HYBRID ACTIVE POWER FILTER UNDER DISTORTED MAINS VOLTAGE CONDITIONS HYBRYDOWY ENERGETYCZNY FILTR AKTYWNY W WARUNKACH ODKSZTAŁCONEGO NAPIĘCIA SIECI ELEKTRYKA 2009 Zeszyt 2 (210) Rok LV Marian PASKO, Dawid BUŁA Instytut Elektrotechniki i Informatyki, Politechnika Śląska w Gliwicach HYBRID ACTIVE POWER FILTER UNDER DISTORTED MAINS VOLTAGE CONDITIONS

Bardziej szczegółowo

ROZPRAWY NR 128. Stanis³aw Mroziñski

ROZPRAWY NR 128. Stanis³aw Mroziñski UNIWERSYTET TECHNOLOGICZNO-PRZYRODNICZY IM. JANA I JÊDRZEJA ŒNIADECKICH W BYDGOSZCZY ROZPRAWY NR 128 Stanis³aw Mroziñski STABILIZACJA W ASNOŒCI CYKLICZNYCH METALI I JEJ WP YW NA TRWA OŒÆ ZMÊCZENIOW BYDGOSZCZ

Bardziej szczegółowo