The analysis of the energy demand for heating and cooling of the house built on the basis of the traditional Canadian wood-frame construction

Podobne dokumenty
PORÓWNANIE METOD STOSOWANYCH DO OKREŚLANIA DŁUGOŚCI OKRESU OGRZEWCZEGO

SZKŁO PIANKOWE JAKO TERMOIZOLACJA PODŁOGI NA GRUNCIE USE OF FOAM GLASS AS A SLAB ON GRADE THERMAL INSULATION

WPŁYW WYKORZYSTANIA INSTALACJI FOTOWOLTAICZNEJ ZASILAJĄCEJ POMPĘ CIEPŁA W OKRESIE OGRZEWCZYM NA WSKAŹNIK EK I EP CHARAKTERYSTYKI ENERGETYCZNEJ BUDYNKU

A BUILDING MADE OF POLYSTYRENE PREFABRICATES FROM THE PERSPECTIVE OF NEW TECHNICAL CONDITIONS AND STANDARDS OF NF15 AND NF40

ROZPRAWA DOKTORSKA. Model obliczeniowy ogrzewań mikroprzewodowych

ROZWIĄZANIA ARCHITEKTONICZNO-BUDOWLANO-INSTALACYJNE A EFEKTYWNOŚĆ ENERGETYCZNA BUDYNKU JEDNORODZINNEGO

ANALIZA PORÓWNAWCZA ZUŻYCIA I KOSZTÓW ENERGII DLA BUDYNKU JEDNORODZINNEGO W SŁUBICACH I FRANKFURCIE NAD ODRĄ

PRACA ZINTEGROWANEGO UKŁADU GRZEWCZO- CHŁODZĄCEGO W BUDYNKU ENERGOOSZCZĘDNYM I PASYWNYM

AN EFFECT OF FLOW NON-UNIFORMITY IN EARTH-TO-AIR MULTI-PIPE HEAT EXCHANGERS (EAHEs) ON THEIR THERMAL PERFORMANCE

TYRE PYROLYSIS. REDUXCO GENERAL DISTRIBUTOR :: ::

Wprowadzenie. Wprowadzenie. Propozycja metody oceny efektywności energetycznej systemów w wentylacji budynków w mieszkalnych.

OKREŚLANIE OPTYMALNEGO UDZIAŁU OKIEN W BUDYNKU MIESZKALNYM

Metody obliczania izolacyjności akustycznej między pomieszczeniami w budynku według PN-EN :2002 i PN-EN :2002

MACIEJ MIJAKOWSKI, JERZY SOWA, PIOTR NAROWSKI

TRANSPORT W RODZINNYCH GOSPODARSTWACH ROLNYCH

Domy inaczej pomyślane A different type of housing CEZARY SANKOWSKI

Po dokonaniu poprawnej instalacji i uruchomieniu powinno wyświetlić się okno dialogowe rys.1

Szafa mroźnicza Freezing cabinet. Typ Type. Dane techniczne Technical data. Model Model SMI 04. SMI 04 Indus. Strona 1/9 Page 1/9

THE IDENTIFICATION OF SELECTED WINDOW ENERGY PARAMETERS IN WINTER AND SUMMER PERIODS IN THE GREATER POLAND REGION

Equipment for ultrasound disintegration of sewage sludge disseminated within the Record Biomap project (Horizon 2020)


Twoje osobiste Obliczenie dla systemu ogrzewania i przygotowania c.w.u.

G14L LPG toroidal tank

Streszczenie rozprawy doktorskiej

Proposal of thesis topic for mgr in. (MSE) programme in Telecommunications and Computer Science

SYMULATION OF NIGHT COOLING IN A SINGLE DWELLING OF A LARGE PANEL BUILDING

KAROLKOWA BUSINESS PARK

Typ VFR. Circular flow adjustment dampers for the adjustment of volume flow rates and pressures in supply air and extract air systems

Analiza porównawcza zmian w rozbiorach wody z uwzględnieniem sposobu jej dostarczania do odbiorców

Typ VFR. Circular flow adjustment dampers for the adjustment of volume flow rates and pressures in supply air and extract air systems

THE INFLUENCE OF THE ENGINE LOAD ON VALUE AND TEMPERATURE DISTRIBUTION IN THE VALVE SEATS OF TURBO DIESEL ENGINE


System optymalizacji produkcji energii

Compression strength of pine wood (Pinus Sylvestris L.) from selected forest regions in Poland, part II

TECHNICAL CATALOGUE WHITEHEART MALLEABLE CAST IRON FITTINGS EE

INFLUENCE OF THERMAL INSULATION AND VENTILATION SYSTEM ON HEAT CONSUMPTION IN A SINGLE-FAMILY HOUSE

DESIGN OF MECHANICAL VENTILATION SYSTEMS EFFICIENT USE OF ENERGY

THE INFLUENCE OF FITTING OF A WINDOW ON A HEAT TRANSFER COEFFICIENT AND AN ENERGY BALANCE OF A BUILDING

CEE 111/211 Agenda Feb 17

PORTS AS LOGISTICS CENTERS FOR CONSTRUCTION AND OPERATION OF THE OFFSHORE WIND FARMS - CASE OF SASSNITZ

Krytyczne czynniki sukcesu w zarządzaniu projektami

WPŁYW TEMPERATURY W POMIESZCZENIACH POMOCNICZYCH NA BILANS CIEPŁA W BUDYNKACH DLA BYDŁA

Sargent Opens Sonairte Farmers' Market

PRODUCTION HALL OFFER

WYKORZYSTANIE METODY ELEMENTÓW SKOŃCZONYCH W MODELOWANIU WYMIANY CIEPŁA W PRZEGRODZIE BUDOWLANEJ WYKONANEJ Z PUSTAKÓW STYROPIANOWYCH

Has the heat wave frequency or intensity changed in Poland since 1950?

SEGRO BUSINESS PARK WARSAW

ROZPRAWY NR 128. Stanis³aw Mroziñski

Warszawa Al. Jerozolimskich przy ul. Badylarskiej

Environment Protection Engineering THERMAL PROCESSES IN SOLAR DOMESTIC HOT-WATER SYSTEM

Analiza porównawcza zapotrzebowania na energię końcową i zużycia energii dla wybranej grupy budynków

Regionalny SEAP w województwie pomorskim

Wpływ czynników atmosferycznych na zmienność zużycia energii elektrycznej Influence of Weather on the Variability of the Electricity Consumption

SYSTEM KONSTRUKCYJNY BUDYNKU A RYZYKO WYSTĄPIENIA STRESU TERMICZNEGO U KRÓW MLECZNYCH

PRÓBY EKSPLOATACYJNE KOMPOZYTOWYCH WSTAWEK HAMULCOWYCH TOWAROWEGO

Network Services for Spatial Data in European Geo-Portals and their Compliance with ISO and OGC Standards

CWF - Piece komorowe ogólnego przeznaczenia

Nazwa lokalizacji Site name Mickiewicza 6 Miasto Town Sieradz Województwo Voivodship lodzkie Powierzchnia całkowita (m 2 ) Area total (sq.

DUAL SIMILARITY OF VOLTAGE TO CURRENT AND CURRENT TO VOLTAGE TRANSFER FUNCTION OF HYBRID ACTIVE TWO- PORTS WITH CONVERSION

OCENA POTRZEB CIEPLNYCH BUDYNKU NA PODSTAWIE MONITORINGU DOSTARCZANEJ ENERGII

Fixtures LED HEDRION

CATALOGUE CARD LEO S L XL / BMS KARTA KATALOGOWA LEO S L XL / BMS

WPŁYW ZMIENNOŚCI DOSTARCZONEJ MOCY CIEPLNEJ NA TEMPERATURĘ POMIESZCZEŃ OGRZEWANYCH

SPIS TREŚCI SPIS WAŻNIEJSZYCH OZNACZEŃ WSTĘP KRÓTKA CHARAKTERYSTYKA SEKTORA ENERGETYCZNEGO W POLSCE... 14

Zarządzanie sieciami telekomunikacyjnymi

EGARA Adam Małyszko FORS. POLAND - KRAKÓW r

Pomiary hydrometryczne w zlewni rzek

Systemy bierne w podnoszeniu efektywności energetycznej budynków użyteczności publicznej symulacje działania.

YAKY, YAKYżo 0,6/1 kv. Kable elektroenergetyczne z izolacją PVC. Norma IEC :2004. Konstrukcja. Zastosowanie. Właściwości

KSZTAŁTOWANIE MIKROKLIMATU W STREFIE PRZEBYWANIA LUDZI W OBIEKTACH SAKRALNYCH

Helena Boguta, klasa 8W, rok szkolny 2018/2019

II wariant dwie skale ocen II alternative two grading scales

y = The Chain Rule Show all work. No calculator unless otherwise stated. If asked to Explain your answer, write in complete sentences.

NIESTACJONARNY PRZEPŁYW CIEPŁA W TŁOKU DOŁADOWANEGO SILNIKA Z ZAPŁONEM SAMOCZYNNYM

Przewody elektroenergetyczne z izolacją XLPE

OCENA JAKOŚCI ENERGETYCZNEJ BUDYNKÓW UŻYTECZNOŚCI PUBLICZNEJ NA PRZYKŁADZIE BIUROWCA ZLOKALIZOWANEGO W LUBLINIE

Strona główna > Produkty > Filtry i wkłady filtracyjne > Obudowy filtrów do montażu kanałowego > Spigots > Typ KSFSSP. Typ KSFSSP

WAREHOUSE AND PRODUCTION HALL OFFER poz. schematu nr 1 position 1 on the sketch

LED WASHER 30x3W WHITE IP65 F

Analiza uszkodzeń systemów chłodniczych jednostek rybackich


WPŁYW SZYBKOŚCI STYGNIĘCIA NA WŁASNOŚCI TERMOFIZYCZNE STALIWA W STANIE STAŁYM

SEGRO BUSINESS PARK LODZ ROKICINSKA 156, 168. SEGRO.pl m 2 / 53,500 sq m

OPTYMALIZACJA STEROWANIA MIKROKLIMATEM W PIECZARKARNI

FIZYKA BUDOWLI W TEORII I PRAKTYCE TOM IX, Nr

ANALIZA TECHNICZNO-EKONOMICZNA ZASTOSOWANIA GRUNTOWEJ I POWIETRZNEJ POMPY CIEPŁA W BUDYNKU JEDNORODZINNYM STUDIUM PRZYPADKU

OPIS KONSTRUKCJI DESIGN DESCRIPTION

DELTA 600 corner left with TÜV certi ed

Wydział Budownictwa, Politechnika Częstochowska Faculty of Civil Engineering, Częstochowa University of Technology

Kreowanie komfortu przy racjonalnym zużyciu energii w świetle certyfikacji LEED i BREEAM

DELTA 600 corner right with TÜV certi ed

YKXS, YKXSżo 0,6/1 kv. Kable elektroenergetyczne z izolacją XLPE. Norma IEC :2004. Konstrukcja. Zastosowanie. Właściwości

YAKXS, YAKXSżo 0,6/1 kv. Kable elektroenergetyczne z izolacją XLPE. Norma IEC :2004. Konstrukcja. Zastosowanie.

Przewody do linii napowietrznych Przewody z drutów okrągłych skręconych współosiowo

RCH 05 Hercules. Dane techniczne Technical data RCH 05. Regał chłodniczy Cooling multideck. Strona 1/8 Page 1/8.

WSCHÓD I ZACHÓD SŁOŃCA SUNRISE / SUNSET

IDENTYFIKACJA PARAMETRÓW CHARAKTERYZUJĄCYCH OBCIĄŻENIE SEKCJI OBUDOWY ZMECHANIZOWANEJ SPOWODOWANE DYNAMICZNYM ODDZIAŁYWANIEM GÓROTWORU

YKY, YKYżo 0,6/1 kv. Kable elektroenergetyczne z izolacją PVC. Norma. 10 mm² PN-HD 603 S1:3G >10 mm² IEC :2004. Konstrukcja.

Transkrypt:

Annals of Warsaw University of Life Sciences - SGGW Forestry and Wood Technology 85, 2014: 40-44 (Ann. WULS - SGGW, For. and Wood Technol. 85, 2014) The analysis of the energy demand for heating and cooling of the house built on the basis of the traditional Canadian wood-frame construction MARIUSZ CYRANKOWSKI, JACEK WILKOWSKI, PIOTR PODZIEWSKI, KAROL SZYMANOWSKI, DAGMARA CHLUDZIŃSKA Faculty of Wood Technology, Warsaw University of Life Sciences - SGGW Abstract: The analysis of the energy demand for heating and cooling of the house built on the basis of the traditional Canadian wood-frame construction. This study shows calculation of demand for power needed for heating and cooling of a house built in compliance with Canadian wood-frame construction technology. Conducted calculations prove that the house erected by traditional Canadian wood-frame construction technology shows lower demand for thermal power than the brick building, while energy consumption on cooling is higher. Keywords: masonry house, Canadian wood-frame construction, energy effectiveness, demand for thermal power PURPOSE AND SCOPE OF THE WORK The aim of the work is to calculate demand for energy needed to heat and cool single family house built on the basis of traditional Canadian wood-frame construction technology using the simplified hourly method. Calculations were conducted in accordance with PN-EN ISO standard 13790:2009 Appropriable energy properties of buildings. Calculation of energy consumption on heating and cooling. The model was based on the data of typical meteorological year, which are available on the website of the Ministry of Transport, Construction and Maritime Economy for Warszawa-Okęcie weather station. MATERIALS AND METHODS Calculation of energy consumption on heating and cooling were performed using hourly method, which mathematical model is simplification of the image of internal and external environment parameters changes used by building energy simulation. Using this mathematical model it is possible to determine the value of heating and cooling power at any time from 8760 hours of typical meteorological year. The internal space of a building is divided into zones, where the parameters of thermal comfort are to be maintained. Decrease or excess of temperature determines the start of heating or cooling system. Values of internal air temperature are variable and determined at any hour of the year. Determination of the following factors is required for the calculations: heat loss through transparent and opaque partitions, coefficients of heat loss through inner surfaces and coefficient of ventilation heat loss. In the simplified hourly method both heat gains and losses through all the exterior coverings (roof, floor on the ground, doors, windows) are taken into account in view of the heat capacity, internal heat gains from people staying in the appropriable area and from electrical equipment, heat loss by long-wave radiation. The calculations are carried out for each of the 8760 hours of the year based on the Warszawa- Okęcie weather station data. The calculated heat balance determines momentary energy consumption on warmth and cold. Access data to the model were based on the technical data of the building, while the using schedule was drawn up based on a typical daily schedule of a family consisting of four people (Narowski, 2013). 40

Table 1. Technical data of a building erected by Canadian wood-frame construction technology. INITIAL DATA Location Warsaw Orientation S Length 16,24 m Width 7,84 m Number of floors 2,00 - Height of floors 4,33 m External temperature -18,00 C Heat transfer coefficient of the external walls 0,176 W/m²K of the external doors and windows 0,600 W/m²K of the roof 0,123 W/m²K of the floor on the ground 0,148 W/m²K Construction of the building light Ventilation multiplicity of exchanges 0,60 1/h Table 2. Characterisation of a building erected by Canadian wood-frame construction technology. Characteristics of the building Length A 16,24 m Width B 7,84 m Number of floors 2,00 - Height H 8,66 m Cubic capacity 897 m³ Usable area 153,910 m² U s 0,176 W/m²K Computational transfer coefficients U ok 0,600 W/m²K U str 0,123 W/m²K U pod 0,148 W/m²K Multiplicity of exchanges 0,60 1/h Number of persons 4 os. Volume of air exchanged Computational internal temperatures 538,2 m³/h Ө int, H, set 20 C Ө int, C, set 26 C coefficient of air repossession by convexion h is 3,45 W/m2K ratio of partitions to floor A at 4,5 - effective are of thermal mass A m 318,304 m2 heat capacity C m 199312794,56 J/K 41

RESULTS Computational thermal power consumption needed to heat the air for the building erected on the basis of Canadian wood-frame construction technology is 1429,79 kwh higher than for a passive house with enhanced thermal insulation of external partitions, wood-based materials and constructional solutions to reduce heat loss through thermal bridges. The power supplied to the building [kwh]*10-1 Internal air temperature C External temperature Graph 1. Energy consumption in a function of internal and external temperatures of the building erected by Canadian wood-frame construction technology without the use of sunshades (Source: Own elaboration). At the same time the amount of energy required for heating was 648,85 kwh lower than in comparison to the traditional brick building using hollow brick and thermal insulations made of 20-cm thick expanded polystyrene. Table 3. Summary of computational thermal power demand for a house built of wood-frame construction without the use of sunshades. Heating Cooling 4420,43 kwh 11553,46 kwh 28,72 kwh/m 2 75,07 kwh/m 2 42

The power supplied to the building [kwh]*10-1 Internal air temperature C External temperature Graph 2. Energy consumption in a function of internal and external temperatures of the building erected by Canadian wood-frame construction technology with the use of sunshades (Source: Own elaboration). Table 4. Summary of computational thermal power demand for a house built of wood-frame construction with the use of sunshades. Heating Cooling 4459,32 kwh 960,98 kwh 28,97 kwh/m 2 6,24 kwh/m 2 CONCLUSIONS On the basis of the results of the conducted calculations the following conclusions has been drawn: 1. The house built on the basis of the Canadian wood-frame construction shows lower demand for thermal power than the brick house. 2. The house built on the basis of the Canadian wood-frame construction has shown the biggest energy consumption on cooling. REFERENCES: 1. Narowski P., 2013: Procedura obliczania rocznego zapotrzebowania na energię do ogrzewania i chłodzenia, Materiały do ćwiczeń z Fizyki Budynków, Wydział Inżynierii Środowiska Politechniki Warszawskiej 2. Chludzińska D., 2013: Analiza porównawcza zapotrzebowania energetycznego na ogrzewanie i chłodzenie dla różnych typów domów jednorodzinnych. Praca magisterska. Warszawa 3. PN-EN ISO 13790: 2009 Energetyczne właściwości użytkowe budynków. Obliczenie zużycia energii na potrzeby ogrzewanie i chłodzenia 43

Streszczenie: "Analiza zapotrzebowania energetycznego na ogrzewanie i chłodzenie domu wzniesionego w oparciu o tradycyjną technologię szkieletu kanadyjskiego". W pracy obliczono zapotrzebowanie na moc potrzebą do ogrzewania i chłodzenia dla budynku mieszkalnego wzniesionego tradycyjną technologią szkieletu kanadyjskiego. Po przeprowadzonych obliczeniach stwierdzono, iż dom postawiony według tradycyjnej technologii szkieletu kanadyjskiego wykazuje niższe zapotrzebowanie na moc cieplną niż budynek murowany, natomiast zużycie energii na cele chłodnicze jej wyższe. Corresponding authors: Mariusz Cyrankowski, Jacek Wilkowski, Piotr Podziewski, Karol Szymanowski, Dagmara Chludzińska Faculty of Wood Technology, Warsaw University of Life Sciences - SGGW 159 Nowoursynowska St. 02-776 Warsaw,Poland e-mail mariusz_cyrankowski@sggw.pl e-mail: jacek_wilkowski@sggw.pl e-mail: piotr_podziewski@sggw.pl e-mail: karol_szymanowski@sggw.pl 44